Page 49 - Sace Emax 2 Catalogue
P. 49

PROTECTION TRIP UNITS                                                            3/25



















                                                                                                                       03
 ABB Code ANSI Code Function  Threshold  Threshold step  Tripping time  Time   Excludibility  Excludibility  Pre-allarm  Trip curve Ekip Touch  Ekip Hi-Touch  Ekip G Touch  Ekip G Hi-Touch
 Step                 trip
 RV  59N  Residual overvoltage protection U22 = 0.05….0.5 x Un 0.001 x Un  with U > U22, t22 =  0.5…120s  0.01s  yes  yes  no  t = k
 Tolerance  ± 5%  The better of the two data: ± 10% or
 ± 40 ms (for t<5s) / ± 100 ms (for t≥5s)
 OP  32OF  Active overpower protection  P26 = 0.4…2 Sn  0.001 Sn  with P > P26, t26 =  0.5…100s  0.5s  yes  yes  no  t = k
 Tolerance  ± 10%  The better of the two data: ± 10% or
 ± 40 ms (for t<5s) / ± 100 ms (for t≥5s)
 OQ  32OF  Reactive overpower protection Q27 = 0.4…2 Sn  0.001 Sn  with Q > Q27, t27 =  0.5…100s  0.5s  yes  yes  no  t = k
 Tolerance  ± 10%  The better of the two data: ± 10% or
 ± 40 ms (for t<5s) / ± 100 ms (for t≥5s)
 UP  32LF  Active underpower protection  P23 = 0.1...1 x Sn  0.001 x Sn  with P < P23, t23 =  0.5…100s  0.5s  yes  yes  no  t = k
 Start up  range: 0.1…30s  0.01s  yes
 Tolerance  ± 10%  The better of the two data: ± 10% or
 ± 40 ms (for t<5s) / ± 100 ms (for t≥5s)
 RQ  40/32R  Loss of field or reverse reactive  Q24 = -1…-0.1 Sn  0.001 Sn  with Q > Q24, t24 =  0.5…100s  0.1s  yes  yes  no  t = k
 power protection  Kq = -2…2  0.01
 Loss of field or reverse reactive  Q25 = -1…-0.1 Sn  0.001 Sn  with Q > Q25, t25 =  0.5…100s  0.5s  yes  yes  no  t = k
 power protection  Kq2 = -2…2  0.01
 Voltage minimum threshold  Vmin. = 0.5...1.2  0.01  yes
 Tolerance  ± 10%  The better of the two data: ± 10% or
 ± 40 ms (for t<5s) / ± 100 ms (for t≥5s)
 S2(V)  51V  Voltage controlled overcurrent  I21 = 0.6...10 x In  0.1 x In  With I > I21, t21 =  0.05…30s  0.01s  yes  yes  no  t = k
 protection
 Step mode  Ul2= 0.2…1 x Un  0.01 x Un
 Ks2= 0.1…1  0.01
 Linear mode   Ul2= 0.2…1 x Un  0.01 x Un
 Uh2= 0.2…1 x Un  0.01 x Un
 Ks2= 0.1…1  0.01
 Tolerance  ± 10%  The better of the two data:
 ± 10% or ± 40 ms (for t<5s) /
 ± 100 ms (for t≥5s)
 ROCOF  81R  Rate of change of frequency   f28 = 0.4….10 Hz/s  0.2 Hz/s  with f > f28, t28 = 0.5...10s   0.01s  yes  yes  no  t = k
 protection
 Trip direction  up &/or down
 Tolerance  ± 5%  The better of the two data:
 ± 20% or ± 200 ms
 Synchro-  25  Synchrocheck (Live busbars)  Ulive = 0.5…1.1 Un   0.001 Un   Stability voltage time   0.001s   yes  only   no  -
 check  SC  ∆U = 0.02…0.12 Un   0.001 Un   for live state = 100...30000ms  0.01 s  signalling
 ∆f = 0.1…1Hz   0.1Hz   Minimum matching Time =
 ∆Φ = 5…50° elt  5° elt  100...3000ms
 Tolerance  ± 10%
 Synchrocheck     Ulive = 0.5…1.1 Un   0.001 Un   tref = 0.1…30s  0.1s  yes  only   no  -
 (Live,Dead busbars)  Udead = 0.02…0.2 Un 0.001 Un  signalling
 Frequency check off  yes
 Phase check off  yes
 Dead bar configuration  Reverse/standard  yes
 Primary voltage  100...1150  100, 115, 120, 190, 208,
 220, 230, 240, 277, 347,
 380, 400, 415, 440, 480,
 500, 550, 600, 660, 690,
 910, 950, 1000, 1150
 Secondary voltage  100...120  100, 110, 115, 120
 Tolerance  ± 10%
 (1) With Vaux all thresholds are available. Without Vaux minimum threshold is limited to: 0.3In (with In = 100A), 0.25In (with In = 400A) or 0.2In (for all other ratings)    (2) 2I Trip time:
 The tolerances above apply to trip units already powered by the main circuit with current flowing in at least two-phases or an auxiliary power supply.   •  < 3ms when the fault current is above 18kA
 In all other cases the following tollerance values apply:   •  7ms (three-phase) or 9ms (single-phase) when the fault current is greater than three times the 2I setting (I31)
           •  ≤ 15ms when the fault current is lower than three times the 2I setting (I31)
          (3) Instantaneous protection can be permanently non-defeatable through the dedicated extracode.
          Key:
          -    not available
              available
              available with the dedicated software package. The Measuring Package has to be activated first, if not provided by default.
             For RC protection, Measurement Enabler with voltage sockets and Ekip Supply are needed.
              available with Ekip Synchrocheck