3/24             SACE EMA X 2 LOW VOLTAGE AIR CIRCUIT-BRE AKERS



          —

          Technical characteristics for protection


          trip units


          Protection functions





          ABB Code ANSI Code Function          Threshold       Threshold step    Tripping time             Time                  Excludibility  Excludibility  Pre-allarm  Trip curve Ekip Touch  Ekip Hi-Touch  Ekip G Touch  Ekip G Hi-Touch
                                                                                                           Step                              trip
          RV     59N     Residual overvoltage protection U22 = 0.05….0.5 x Un 0.001 x Un  with U > U22, t22 =  0.5…120s  0.01s   yes         yes      no            t = k
                         Tolerance             ± 5%                              The better of the two data: ± 10% or
                                                                                 ± 40 ms (for t<5s) / ± 100 ms (for t≥5s)
          OP     32OF    Active overpower protection  P26 = 0.4…2 Sn  0.001 Sn   with P > P26, t26 =  0.5…100s  0.5s             yes         yes      no            t = k
                         Tolerance             ± 10%                             The better of the two data: ± 10% or
                                                                                 ± 40 ms (for t<5s) / ± 100 ms (for t≥5s)
          OQ     32OF    Reactive overpower protection Q27 = 0.4…2 Sn  0.001 Sn  with Q > Q27, t27 =  0.5…100s  0.5s             yes         yes      no            t = k
                         Tolerance             ± 10%                             The better of the two data: ± 10% or
                                                                                 ± 40 ms (for t<5s) / ± 100 ms (for t≥5s)
          UP     32LF    Active underpower protection  P23 = 0.1...1 x Sn  0.001 x Sn  with P < P23, t23 =  0.5…100s  0.5s       yes         yes      no            t = k
                         Start up                                                range: 0.1…30s            0.01s                 yes
                         Tolerance             ± 10%                             The better of the two data: ± 10% or
                                                                                 ± 40 ms (for t<5s) / ± 100 ms (for t≥5s)
          RQ     40/32R  Loss of field or reverse reactive  Q24 = -1…-0.1 Sn  0.001 Sn  with Q > Q24, t24 =  0.5…100s  0.1s      yes         yes      no            t = k
                         power protection      Kq = -2…2       0.01
                         Loss of field or reverse reactive  Q25 = -1…-0.1 Sn  0.001 Sn  with Q > Q25, t25 =  0.5…100s  0.5s      yes         yes      no            t = k
                         power protection      Kq2 = -2…2      0.01
                         Voltage minimum threshold  Vmin. = 0.5...1.2  0.01                                                      yes
                         Tolerance             ± 10%                             The better of the two data: ± 10% or
                                                                                 ± 40 ms (for t<5s) / ± 100 ms (for t≥5s)
          S2(V)  51V     Voltage controlled overcurrent  I21 = 0.6...10 x In  0.1 x In  With I > I21, t21 =  0.05…30s  0.01s     yes         yes      no            t = k
                         protection
                         Step mode             Ul2= 0.2…1 x Un  0.01 x Un
                                               Ks2= 0.1…1      0.01
                         Linear mode           Ul2= 0.2…1 x Un  0.01 x Un
                                               Uh2= 0.2…1 x Un  0.01 x Un
                                               Ks2= 0.1…1      0.01
                         Tolerance             ± 10%                             The better of the two data:
                                                                                 ± 10% or ± 40 ms (for t<5s) /
                                                                                 ± 100 ms (for t≥5s)
          ROCOF  81R     Rate of change of frequency   f28 = 0.4….10 Hz/s  0.2 Hz/s  with f > f28, t28 = 0.5...10s   0.01s       yes         yes      no            t = k
                         protection
                         Trip direction        up &/or down
                         Tolerance             ± 5%                              The better of the two data:
                                                                                 ± 20% or ± 200 ms
          Synchro-  25   Synchrocheck (Live busbars)  Ulive = 0.5…1.1 Un   0.001 Un   Stability voltage time   0.001s            yes         only     no            -
          check  SC                            ∆U = 0.02…0.12 Un   0.001 Un      for live state = 100...30000ms  0.01 s                      signalling
                                               ∆f = 0.1…1Hz    0.1Hz             Minimum matching Time =
                                               ∆Φ = 5…50° elt  5° elt            100...3000ms
                         Tolerance             ± 10%
                         Synchrocheck          Ulive = 0.5…1.1 Un   0.001 Un     tref = 0.1…30s            0.1s                  yes         only     no            -
                         (Live,Dead busbars)   Udead = 0.02…0.2 Un 0.001 Un                                                                  signalling
                         Frequency check off                                                                                     yes
                         Phase check off                                                                                         yes
                         Dead bar configuration  Reverse/standard                                                                yes
                         Primary voltage       100...1150      100, 115, 120, 190, 208,
                                                               220, 230, 240, 277, 347,
                                                               380, 400, 415, 440, 480,
                                                               500, 550, 600, 660, 690,
                                                               910, 950, 1000, 1150
                         Secondary voltage     100...120       100, 110, 115, 120
                         Tolerance             ± 10%
          (1) With Vaux all thresholds are available. Without Vaux minimum threshold is limited to: 0.3In (with In = 100A), 0.25In (with In = 400A) or 0.2In (for all other ratings)
          The tolerances above apply to trip units already powered by the main circuit with current flowing in at least two-phases or an auxiliary power supply.
          In all other cases the following tollerance values apply:
          ABB Code      Trip threshold       Trip time
          L             Trip between 1.05 and 1.2 x I1 ± 20%
          S             ± 10%                ± 20%
          I             ± 15%                ≤ 60ms
          G             ± 15%                ± 20%
          Other protection  ± 15%            ± 20%