3/26             SACE EMA X 2 LOW VOLTAGE AIR CIRCUIT-BRE AKERS



          —

          Technical characteristics for protection


          trip units


          Measurement functions












          Instantaneous measurements                       Displayed with   Parameters                                           Precision                                  Standard                        Ekip Dip
                                                           Ekip Multimeter
          Currents (RMS)                             [A]   •             L1, L2, L3, Ne                                          1%                                         IEC 61557-12
          Earth fault current (RMS)                  [A]   •             Ig                                                      2%

          Record of values: of the parameter for each interval with time-stamping  Parameters                                    Window                                     Intervals
          Current: minimum and maximum               [A]   •             I Min, I Max                                            Fixed, synchronizable by remote            Duration: 5…120min
                                                                                                                                                                            Number of intervals: 24

          Information on trip and opening data: after a fault with or without auxiliary supply  Parameters
          Type of protection tripped                       •             eg. L, S, I, G
          Fault values per phase                     [A]   •             eg. I1, I2, I3, neutral for S protection
          Time-stamping                                    •             Date, time and progressive number

          Maintenance indicators                                         Parameters
          Information on last 30 trips                     •             Type of protection, fault values and time-stamping
          Information on last 200 events                   •             Type of event, time-stamping
          Number of mechanical operations  (1)       [no]  •             Can be associated to alarm
          Total number of trips                      [no]  •
          Total operating time                       [h]   •
          Wear of contacts                           [%]   •             Prealarm >80%, Alarm = 100%
          Date of maintenance operations performed         •             Last
          Indication of maintenance operation needed       •
          Circuit-breaker I.D.                             •             Type of circuit breaker, assigned device name,
                                                                         serial number

          Self-diagnosis                                                 Parameters
          Check of continuity of internal connections      •             Alarm due to disconnection: rating plug, sensors,
                                                                         trip coil                                               Note:
          Failure of circuit breaker to open (ANSI 50BF)   •             Alarm following non-tripping of protection functions    Opening of circuit breaker  can be set in the event of alarm
          Temperature (T)                                  •             Pre-alarm and alarm for abnormal temperature
          (1) with auxiliary supply present