PROTECTION TRIP UNITS                                                            3/29



















                                                                                                                       03







 Instantaneous measurements  Parameters  Precision (Class 1)  Ekip Touch *  Ekip Hi-Touch  Ekip G Touch *  Ekip G Hi-Touch
                                                              ( )
                                                                                            ( )
 Currents (RMS)  [A]  L1, L2, L3, Ne  0.5%
 Earth fault current (RMS)  [A]  Ig  2%
 Phase-phase voltage (RMS)  [V]  U12, U23, U31  0.5%
 Phase-neutral voltage (RMS)  [V]  U1, U2, U3  0.5%
 Phase sequence
 Frequency  [Hz]  f  0.1%
 Active power  [kW]  P1, P2, P3, Ptot  1%
 Reactive power  [kVAR]  Q1, Q2, Q3, Qtot  2%
 Apparent power  [KVA]  S1, S2, S3, Stot  1%
 Power factor  total  2%
 Peak factor  L1, L2, L3, Ne

 Counters recorded from installation or from the last reset  Parameters  Precision (Class 1)
 Active energy  [kWh]  Ep total, Ep positive, Ep negative  1%
 Reactive energy  [kVARh]  Eq total, Ep positive, Ep negative  2%
 Apparent energy  [KVAh]  Es total  1%

 Network Analyzer  Parameters  Intervals
 Hourly average voltage value  [V]   - Umin= 0.75…0.95 x Un   t = 5…120min
 [no]  - Umax= 1.05…1.25 x Un
 - Events counter (nr. of events day by day in the last year plus the
 total events in the breaker's lifetime)
 Short voltage interruptions  [no]  - Umin= 0.75…0.95 x Un   t <40ms
 - Events counter (nr. of events day by day in the last year plus the
 total events in the breaker's lifetime)
 Short voltage spikes  [no]  - Umax= 1,05…1,25 x Un   t <40ms
 - Events counter (nr. of events day by day in the last year plus the
 total events in the breaker's lifetime)
 Slow-voltage sags and swells  [no]  - Umin1= 0.75…0.95 x Un   t = 0.02s...60s
 - Umin2= 0.75…0.95 x Un
 - Umin3= 0.75…0.95 x Un
 - Umax1= 1.05…1.25 x Un
 - Umax2= 1.05…1.25 x Un
 - Events counter (nr. of events day by day in the last year plus the
 total events in the breaker's lifetime)
 Voltage unbalance  [V]   - U neg. seq.= 0.02…0.10 x Un   t = 5…120min
 [no]  - Events counter (nr. of events day by day in the last year plus the
 total events in the breaker's lifetime)
 Harmonic analysis  Current and Voltage
 - up to 50°
 - Alarm THD: 5…20%
 - Single harmonic alarm:
   3...10% plus a count of minutes the harmonic has been exceeded
          (*) Precision (Class 1) available with dedicated extracode
          With no Class 1, please refer to the precision values below:
          Current (RMS)          1%         Frequency               0.2%       Power factor            2%
          Earth fault current (RMS)  2%     Active power            2%         Active energy           2%
          Phase-phase voltage (RMS)  0.5%   Reactive power          2%         Reactive energy         2%
          Phase-neutral voltage (RMS)  0.5%  Apparent power         2%         Apparent energy         2%