Page 52 - Sace Emax 2 Catalogue
P. 52

3/28             SACE EMA X 2 LOW VOLTAGE AIR CIRCUIT-BRE AKERS



          —

          Technical characteristics for protection


          trip units


          Measurement functions












          Instantaneous measurements                               Parameters                                                    Precision (Class 1)                        Ekip Touch *   Ekip Hi-Touch  Ekip G Touch *  Ekip G Hi-Touch
                                                                                                                                                                                     ( )
                                                                                                                                                                                                                   ( )
          Currents (RMS)                       [A]                 L1, L2, L3, Ne                                                0.5%
          Earth fault current (RMS)            [A]                 Ig                                                            2%
          Phase-phase voltage (RMS)            [V]                 U12, U23, U31                                                 0.5%
          Phase-neutral voltage (RMS)          [V]                 U1, U2, U3                                                    0.5%
          Phase sequence
          Frequency                            [Hz]                f                                                             0.1%
          Active power                         [kW]                P1, P2, P3, Ptot                                              1%
          Reactive power                       [kVAR]              Q1, Q2, Q3, Qtot                                              2%
          Apparent power                       [KVA]               S1, S2, S3, Stot                                              1%
          Power factor                                             total                                                         2%
          Peak factor                                              L1, L2, L3, Ne

          Counters recorded from installation or from the last reset  Parameters                                                 Precision (Class 1)
          Active energy                        [kWh]               Ep total, Ep positive, Ep negative                            1%
          Reactive energy                      [kVARh]             Eq total, Ep positive, Ep negative                            2%
          Apparent energy                      [KVAh]              Es total                                                      1%

          Network Analyzer                                         Parameters                                                    Intervals
          Hourly average voltage value         [V]                 - Umin= 0.75…0.95 x Un                                        t = 5…120min
                                               [no]                - Umax= 1.05…1.25 x Un
                                                                   - Events counter (nr. of events day by day in the last year plus the
                                                                   total events in the breaker's lifetime)
          Short voltage interruptions          [no]                - Umin= 0.75…0.95 x Un                                        t <40ms
                                                                   - Events counter (nr. of events day by day in the last year plus the
                                                                   total events in the breaker's lifetime)
          Short voltage spikes                 [no]                - Umax= 1,05…1,25 x Un                                        t <40ms
                                                                   - Events counter (nr. of events day by day in the last year plus the
                                                                   total events in the breaker's lifetime)
          Slow-voltage sags and swells         [no]                - Umin1= 0.75…0.95 x Un                                       t = 0.02s...60s
                                                                   - Umin2= 0.75…0.95 x Un
                                                                   - Umin3= 0.75…0.95 x Un
                                                                   - Umax1= 1.05…1.25 x Un
                                                                   - Umax2= 1.05…1.25 x Un
                                                                   - Events counter (nr. of events day by day in the last year plus the
                                                                   total events in the breaker's lifetime)
          Voltage unbalance                    [V]                 - U neg. seq.= 0.02…0.10 x Un                                 t = 5…120min
                                               [no]                - Events counter (nr. of events day by day in the last year plus the
                                                                   total events in the breaker's lifetime)
          Harmonic analysis                                        Current and Voltage
                                                                   - up to 50°
                                                                   - Alarm THD: 5…20%
                                                                   - Single harmonic alarm:
                                                                     3...10% plus a count of minutes the harmonic has been exceeded
                                                                                                                                 (*) Precision (Class 1) available with dedicated extracode
                                                                                                                                 With no Class 1, please refer to the precision values below:
   47   48   49   50   51   52   53   54   55   56   57