Page 125 - Sace Emax 2 Manual for design engineers
P. 125

ABB | SACE Emax 2
            Over V Th and Under V Th Certain counters relating to the sequence measurements are available in the Counters - Day -1 and Counters
                                    - Cumulative submenus:
                                     Counters       Description
                                                    Counts the number of times that the average value of the positive sequence (in
                                                    the set direction of rotation of the phases: 1-2-3) or negative sequence (in the set
                                     Over V Th
                                                    direction of rotation of the phases: 3-2-1) exceeds the V Threshold High threshold.
                                                    The count refers to the reference menu interval (previous day or cumulative)
                                                    Counts the number of times that the average value of the positive sequence (in
                                                    the set direction of rotation of the phases: 1-2-3) or negative sequence (in the set
                                     Under V Th
                                                    direction of rotation of the phases: 3-2-1) falls below the V Threshold Low threshold.
                                                    The count refers to the reference menu interval (previous day or cumulative)

                                    Additional List

                                     Counters (Over Voltage)  Description
                                     Last time stamp       Date and time of last recording of the Over V Th counter
                                     Last value            Value of the last swell above the Over V Th [V] threshold
                                     Actual number of O.   Over V Th count for the current day
                                     Actual [day -2 ... day -7]   Over V Th count of the last seven days of activity, calculated using the
                                     number of O.          internal clock of the unit
                                     Counters (Under Voltage) Description
                                     Last time stamp       Date and time of last recording of the Under V Th counter
                                     Last value            Value of the last sag below the Under V Th [V] threshold
                                     Actual number of O.   Under V Th count for the current day
                                     Actual [day -2 ... day -7]   Under V Th count of the last seven days of activity, calculated using the
                                     number of O.          internal clock of the unit




           V microinterr. (Interruption) The V microinterr counter should be understood as reduction of the RMS value of the line-to-line voltage
                                    below the V microinterr. Th set threshold for less than 40 ms (short time voltage sag).
                                    The counter is available in the two submenus Counters - Day -1 and Counters - Cumulative (previous day or
                                    cumulative)
                                           NOTE: Since the counter is based on the RMS value calculation, two rapid voltage sags of
                                               equal duration may be evaluated differently, depending on when they occur:
                                              Drop detected                        Drop not detected






                                                     t                               t







                                    Additional List
                                     Counters           Description
                                     (Interruptions)
                                     Last instant       Date and time of last recording of the V microinterr counter
                                     Last value         Value of last sag below the V microinterr  [V] threshold
                                     Last duration      Value of last sag below the V microinterr  [ms] threshold
                                     Actual number of I.  V microinterr count for the current day
                                     Actual [day -2 ... day -7]  V microinterr count of the last seven days of activity, calculated using the
                                     number of I.       internal clock of the unit







       123 | © 2020 ABB |  1SDH001330R1002 - ECN000134959 - Rev. A                    Ekip Touch - Measurements | 5 - Network Analyzer