Page 127 - Sace Emax 2 Manual for design engineers
P. 127
Continued from the previous page ABB | SACE Emax 2
Counters Description
(Sags Middle)
Last time stamp Date and time of last recording of the Sags Middle counter
Sags Middle Value of last sag below the Sags Middle [V] threshold
Sags Long Duration of last sag below the Sags Middle [ms] threshold
Actual number of S. Sags Middle count of the current day
Actual [day -2 ... day -7] Sags Middle count of the last seven days of activity, calculated using the
number of S. internal clock of the unit
Counters
(Sags Middle) Description
Last time stamp Date and time of last recording of the Sags Long counter
Sags Middle Value of last sag below the Sags Long[V] threshold
Sags Long Duration of last sag below the Sags Long[ms] threshold
Actual number of S. Sags Long count of the current day
Actual [day -2 ... day -7] Sags Long count of the last seven days of activity, calculated using the internal
number of S. clock of the unit
Swells Certain counters relating to swells are available in the Counters - Day -1 and Counters - Cumulative submenus:
Counters
(Sags Middle) Description
Counts the number of times that any line-to-line voltage exceeds the V swell Th
Swells Short
Short threshold for longer than V swell dur Short
Counts the number of times that any line-to-line voltage exceeds the V swell Th
Swells Long
Long threshold for longer than V swell dur Long
The count refers to the reference menu interval (previous day or cumulative)
NOTE: since an event may fall under more than one category, only the counter of the main
type (long > short) is increased
Additional List
Counters
(Swells Short) Description
Last time stamp Date and time of last recording of the Swells Short counter
Last value Value of last swell above Swells Short [V] threshold
Last duration Duration of last swell above Swells Short[ms] threshold
Actual number of S. Swells Short count for the current day
Actual [day -2 ... day -7] Swells Short count of the last seven days of activity, calculated using the
number of S. internal clock of the unit
Counters
(Swells Long) Description
Last time stamp Date and time of last recording of the Swells Long counter
Last value Value of last swell above Swells Long[V] threshold
Last duration Duration of last swell above Spikes[ms] threshold
Actual number of S. Swells Long count for the current day
Actual [day -2 ... day -7] Swells Long count of the last seven days of activity, calculated using the
number of S. internal clock of the unit
125 | © 2020 ABB | 1SDH001330R1002 - ECN000134959 - Rev. A Ekip Touch - Measurements | 5 - Network Analyzer