Continued from the previous page                                   ABB | SACE Emax 2
                                     LEDs     Description
                                              Signals the on status and correct communication with Ekip Touch:
                                               • off: module off
                                               • on steady or flashing synchronized with the Power led of Ekip Touch: module on and
                                     Power
                                              communication with Trip unit present.
                                               • flashing not synchronized with the Power led of Ekip Touch (2 fast flashes per second):
                                              module on and communication with Trip unit absent.
                                              Indicates the status of the communication between network master and module (slave):
                                     Rx        • off: communication between master and module not activated
                                               • on steady: communication between master and module activated
                                              Indicates the status of the communication between network master and module (slave):
                                     Tx        • off: communication between master and module not activated
                                               • on flashing: communication between master and module activated




                      Configurations Resistors can be connected to the RS-485 bus by configuring the dip-switches at the side of the module:



                                                                                                    ON



                                                                                                   1  2  3  4



                                    Figure 126

                                     Resistor   Dip        Description                                      Default
                                                           220 Ω termination resistor
                                     Rterm      1 and 2                                                     Off
                                                           Move dip-switches 1 and 2 to the ON position to connect Rterm
                                                           390 Ω pull-up or pull-down resistor
                                     Rpol       3 and 4                                                     Off
                                                           Move dip-switches 3 and 4 to the ON position to connect Rpol

                                           IMPORTANT: move the dip-switches before connecting the module to Ekip Supply
                                               and the communication network



                              Menu Local bus activation, which is essential for starting the communication between module and Ekip Touch, is
                                    available in the Settings menu (page 46).
                                    Two areas are activated if Ekip Touch detects the module correctly:
                                     •  information area in the About - Modules menu, containing the software version and serial number of the
                                       module
                                     •  specific configuration area in the Settings - Modules menu, where the following communication parameters
                                       can be configured:
                                     Parameter  Description                                             Default
                                                Module address; 1 to 126 range available
                                     Serial address  IMPORTANT: devices connected to the same network must   125 / 124  (1)
                                                    have different addresses


                                    (1)  125 default of the Ekip Com Profibus DP module; 124 default of the Ekip Com Profibus DP
                                    Redundant module


                 Remote information Certain additional information concerning the version and status of the module is available via the service
                                    connector (via Ekip Connect) or by communication via system bus; the information includes: HW and Boot
                                    version, CRC status (correctness of the SW in the module).










       195 | © 2020 ABB |  1SDH001330R1002 - ECN000134959 - Rev. A                External electronic accessories | 3 - Ekip Com Profibus DP