Page 198 - Sace Emax 2 Manual for design engineers
P. 198

ABB | SACE Emax 2
       4 - Ekip Com DeviceNet        TM



                                    Ekip Com DeviceNet  is a communication accessory which allows Ekip Touch to be integrated into a CAN
                                                    TM
                                    network with DeviceNet  communication protocol, with remote supervision and monitoring functions.
                                                      TM
                                    The module is configured as a Slave and remotely, you can:
                                     •  read Ekip Touch measurements and information
                                     •  manage certain controls, including opening and closing the actuator (MOE-E)
                                     •  access information and parameters not available on the display
                                     •  If connected to a withdrawable version of the circuit-breaker, the allows the racked-in/racked-out status
                                       to be detected
                                           NOTE: the remote open and close commands of the circuit-breaker can only be executed if
                                               Ekip Touch is in the Remote configuration and the circuit-breaker is equipped with the
                                           Ekip Com Actuator module (page 234)

                                                    TM
                                    Ekip Com DeviceNet  is always supplied with contacts Ekip AUP and Ekip RTC (page 234).
                                    The System Interface document is available for mapping the module in its communication network. All the
                                    required communication and command details are listed in the document (page 182).


                            Models Two different modules compatible with the DeviceNet  protocol are available: Ekip Com DeviceNet  and
                                                                            TM
                                                                                                              TM
                                    Ekip Com DeviceNet  Redundant.
                                                    TM
                                    The modules are identical in terms of characteristics and installation methods, except for: display menus,
                                    cabling and addresses for system communication, which are specific for each module.
                                           NOTE: if different indications are not given, the information in the next chapter is valid for
                                               both models
                                    The two modules can be connected at the same time to Ekip Touch so as to expand the potential of the unit
                                    (e.g. for applications where high grid reliability is required).

                                           IMPORTANT: each Ekip Touch can be fitted with only one module per type. The
                                               configuration with two modules of the same model is not allowed (example: two
                                           Ekip Com DeviceNetTM Redundant)



                       Connections The module must be assembled in the first vacant slot of the terminal box after Ekip Supply, either on the
                                    circuit-breaker (fixed version) or on the fixed part (withdrawable version).
                                    For references about the connection and terminals, please consult document  1SDM000091r0001; use
                                    Belden 3084A type cables or equivalent for the external cabling.
                                    To connect the module to Ekip Touch, please consult document 1SDH001000r0512.



                       Power supply Ekip Com DeviceNet  is supplied directly by the Ekip Supply module to which it is connected.
                                                    TM
                                    To function correctly, the DeviceNet  bus must be supplied on terminals V+ and V- with a signal of over 12
                                                               TM
                                    VDC.
                                           NOTE:
                                            •  the ABB PLC with DeviceNet (CM575-DN) communication module provides V+ V- supply
                                            •  communication between Ekip Touch and the module is interrupted in the absence of power
                                              supplies from Ekip Supply and on the supply terminals of the bus




















       196 | © 2020 ABB |  1SDH001330R1002 - ECN000134959 - Rev. A              External electronic accessories | 4 - Ekip Com DeviceNet TM
   193   194   195   196   197   198   199   200   201   202   203