Page 200 - Sace Emax 2 Manual for design engineers
P. 200

ABB | SACE Emax 2
                              Menu Local bus activation, which is essential for starting the communication between module and Ekip Touch, is
                                    available in the Settings menu (page 46).
                                    Two areas are activated if Ekip Touch detects the module correctly:
                                     •  information area in the About - Modules menu, containing the software version and serial number of the
                                       module
                                     •  specific configuration area in the Settings - Modules menu, where the following communication parameters
                                       can be configured:
                                     Parameter    Description                                         Default
                                                  Module address; 1 to 63 range available
                                     MAC Address      IMPORTANT: devices connected to the same network must  63 / 62  (1)
                                                     have different addresses
                                                  Data transmission speed; 3 options are available: 125 kbit/s, 250
                                     Baudrate                                                         125 kbit/s
                                                  kbit/s, 500 kbit/s

                                    (1)  63 default of the Ekip Com DeviceNet  TM  module; 62 default of the Ekip Com DeviceNet  TM  Redundant
                                    module


              Remote configurations Additional parameters can be accessed via the service connector (via Ekip Connect) or via a system bus
                                    communication:
                                     Parameter    Description                                         Default
                                     Class ID     Defines the addressing class of the module, either 8 or 16 bits.  8-bit Class ID
                                                  Defines the behavior of the module following loss of communication
                                     Bus-Off      (Bus-Off), with a choice between Standard (supply reset is awaited   DeviceNet
                                     Behavior     if the communication is lost) and Advanced (the module attempts to   standard
                                                  reset itself if it detects the error status).




                 Remote information Certain additional information concerning the version and status of the module is available via the service
                                    connector (via Ekip Connect) or by communication via system bus; the information includes: HW and Boot
                                    version, CRC status (correctness of the SW in the module).















































       198 | © 2020 ABB |  1SDH001330R1002 - ECN000134959 - Rev. A              External electronic accessories | 4 - Ekip Com DeviceNet TM