                       Connections The module must be assembled in the first vacant slot of the terminal box after Ekip Supply, either on the
                                    circuit-breaker (fixed version) or on the fixed part (withdrawable version).
                                    For references about the connection and terminals, please consult document 1SDM000091r0001; a cable
                                    of the Class 6 S/FTP type (Class 6 with double screening S/FTP) must be used for the communication bus.
                                    To connect the module to Ekip Touch, please consult document 1SDH001000r0514.


                       Power supply Ekip Com Modbus TCP is supplied directly by the Ekip Supply module to which it is connected.
                                           NOTE: communication between Ekip Touch and the module is interrupted in the absence of
                                               auxiliary power supply



                           Interface the module has three signaling leds:
                                                             2                          1











                                    Figure 129

                                     LEDs         Description
                                                  Signals the on status and correct communication with Ekip Touch:
                                                   • off: module off
                                                   • on steady or flashing synchronized with the Power led of Ekip Touch: module on and
                                     Power
                                                  communication with Trip unit present.
                                                   • flashing not synchronized with the Power led of Ekip Touch (2 fast flashes per
                                                  second): module on and communication with Trip unit absent.
                                                  Indicates the communication state:
                                     Link (1)      • off: incorrect connection, signal absent.
                                                   • on steady: connection correct
                                                  Indicates the communication state:
                                     Activity (2)   • off: no activity on line
                                                   • flashing: activity on line present (receiving and/or transmitting)