Page 203 - Sace Emax 2 Manual for design engineers
P. 203

ABB | SACE Emax 2
             Configurations via menu Local bus activation, which is essential for starting the communication between module and Ekip Touch, is
                                    available in the Settings menu (page 127).
                                    The following communication parameters can be configured if the module has been correctly detected by
                                    Ekip Touch in the Settings-Modules menu:
                                     Parameter    Description                                         Default
                                                  Defines whether the module has the dynamic (Off) or static (On) IP
                                     Static IP
                                     address ON   address.                                            Off
                                                  Se = On all the associated parameters are enabled
                                     Static address   Enables the static IP to be selected            0.0.0.0
                                     IP address
                                     Static Network   Enables the subnet mask to be selected          0.0.0.0
                                     Mask
                                     Static Gateway  When there are several subnets, enables the IP address of the node to   0.0.0.0
                                     address      which the module is connected to be selected



                 Information in menu The following information will be available in the About-Modules menu if Ekip Touch has detected the module
                                    correctly:
                                     About          Description
                                     SN and version  Identifier and SW version of the module
                                                    Address of the module, assigned to the module by a DHCP server at the time of
                                                    connection to the network in the case of configuration with a dynamic IP, or can be
                                     IP address     xset via the menu in the event of a static IP.
                                                        NOTE: without a DHCP server, the module automatically adopts a random IP
                                                        address within the 169.254.xxx.xxx range
                                                    Subnet mask; identifies the method for recognizing the subnet to which the modules
                                     Network Mask
                                                    belong and enables modules to be searched for within a defined set of recipients.
                                                    IP address of the node to which the module is connected, in the presence of several
                                     Gateway address
                                                    subnets
                                     TCP Client 1, 2, 3  IP addresses of the client devices connected to the module (in the Server mode)
                                                    Address assigned by ABB, with OUI (Organizationally Unique Identifier) equal to
                                     MAC address
                                                    ac:d3:64, which uniquely identifies the manufacturer of an Ethernet device











































       201 | © 2020 ABB |  1SDH001330R1002 - ECN000134959 - Rev. A               External electronic accessories | 5 - Ekip Com Modbus TCP