                                    The tables listing the available voltages and the electrical characteristics are provided below:
                                     Available voltages (Un)   General characteristics   YU
                                     24 V AC/DC                Inrush power (Ps)         300 VA/W
                                     30 V AC/DC                Continuous power (Pc)     3.5 VA/W
                                     48 V AC/DC                Opening time              50 ms
                                     60 V AC/DC
                                     110…120 V AC/DC
                                     220…240 V AC/DC
                                     240...250 V AC/DC
                                     277 V AC/DC
                                     380…400 V AC
                                     415…440 V AC
                                     480…500 V AC

                                    YU: Connections
                                    More details are available in the website http://www.abb.com/abblibrary/DownloadCenter/, which also
                                    includes the entire circuit diagram 1SDM000091r0001.
                                    Information on the assembly is available on the website http://www.abb.com/abblibrary/DownloadCenter/,
                                    in particular for E1.2 in the kit sheet  1SDH000999r0504 and for E2.2-E4.2-E6.2 in the kit sheet
                                    1SDH001000r0504.


            YR: Remote resetting coil
                                    The remote resetting coil deactivates the lock at the closing of the circuit-breaker, generated by the opening
                                    of the circuit-breaker caused by tripping of the Ekip protection trip unit.



                                                             R1

                                                             R2


                                                             YR


                                    YR for E1.2



                                                                R1
                                                                R2


                                                                YR



                                    YR for E2.2 - E4.2 - E6.2
                                    The tables listing the available voltages and the electrical characteristics are provided below:
                                     Available voltages (Un)          General characteristics
                                     24 V AC  (1)   24 V DC  (1)      Operating limits           90...110 %Un
                                     110 V AC  (1)  110 V DC  (1) (2)
                                     220 V AC  (1)  220 V DC  (1) (2)

                                    (1)  The coil must be activated by a pulse lasting at least 20ms.
                                    (2)  The coil must be activated by a pulse lasting max 50ms.
                                    YR: Connections
                                    More details are available in the website http://www.abb.com/abblibrary/DownloadCenter/, which also
                                    includes the entire circuit diagram 1SDM000091r0001.
                                    Information on the assembly is available on the website http://www.abb.com/abblibrary/DownloadCenter/,
                                    in particular for E1.2 in the kit sheet  1SDH000999r0606 and for E2.2-E4.2-E6.2 in the kit sheet
                                    1SDH001000r0606.

       238 | © 2020 ABB |  1SDH001330R1002 - ECN000134959 - Rev. A                 Electrical accessories | 1 - Electrical control accessories