                                    Configuration
                                    To correctly configure the selectivity network of one or more protections:
                                     1. Connect zone selectivity outputs of the same type (example: Szo) of devices belonging to the same zone,
                                    to the zone selectivity input of the device immediately upstream (example: Szi).
                                     2. Connect all the Szc of devices in the same network together.
                                     3. Time t2 must be configured at t2 sel + 50 ms or more, with the exclusion of the device further along its
                                    network.
                                    Logic table
                                    The table includes all cases in which, with zone selectivity enabled in the device, an alarm condition occurs
                                    or a zone selectivity signal is received from another device.
                                           NOTES:

                                            •  the table gives the S protection cases, but is also valid for the other protections: G, S2, I, Gext
                                              and MDGF, each with its respective connections
                                            •  if the selectivities of protections that share the same connections are active at the same time
                                              (example: S, S2 and I), the inputs/outputs are managed with OR logic
                                     Condition   Szi   Szo   Tripping time Remarks
                                     If < I2     0     0     No TRIP     TRIP Il device not in alarm status
                                                                         The device is not in the alarm status, but sends the
                                     If < I2     1     1     No TRIP
                                                                         selecitivity signal received from the device upstream
                                                                         The device is in the alarm status and is the first to detect
                                     If > I2     0     1     t2 sel  (1)
                                                                         the fault: trips within time t2 sel  (1)
                                                                         The device is in the alarm status but is not the first to
                                     If > I2     1     1     t2  (2)
                                                                         detect the fault: trips within time t2  (2)
                                    (1)  the trip time of protection I is that of protection
                                    (2)  for I protection tripping time is 100ms


         D zone selectivity Protection Foreword
                                    This function, which can be activated for D protection (if available and enabled), enables devices belonging
                                    to the same installation (including Ekip Touch) to be connected together so as to handle the trip commands
                                    in a better way in the case of D protection.
                                    It is especially useful in ring and grid type systems where, besides the zone, it is essential to also define the
                                    direction of the power flow that supplies the fault.
                                    The function allows the devices to be coordinated so that, if a fault occurs:
                                     •  The device nearest to the fault trips
                                     •  The other devices are blocked for a programmable time
                                           NOTES:
                                            •  connection can be made between ABB devices that have the zone selectivity function
                                            •  disable the zone selectivities of protections S, S2, I, G, Gext and MDGF to correctly use the
                                              selectivity D function
                                    Characteristics
                                    Ekip Touch has five selectivity connections, located on the upper terminal box of the CB:
                                     Name       Type       Description                       Denomintion for D
                                     Szi        Input      Forward direction selectivity input  DFin
                                     Szo        Output     Forward direction selectivity output  DFout
                                     Gzi        Input      Backward direction selectivity input  Dbin
                                     Gzo        Output     Backward direction selectivity output  Dbout
                                     Szc        Common     Common connection of selectivity network  SZc