Page 72 - SACE Tmax XT - Catalogue
P. 72

t
          t
             state
          3/38 steady I7  start-up t7  I  SACE TMAX XT LOW VOLTAGE MOLDED CASE CIRCUIT-BREAKERS
                       I
          —  100% 200% L
          t t
            50% 150%
          Ekip Touch/Hi-Touch
               I7
                    S
                       I
                     t7
          Protection functions
                       I I
          t t  steady  start-up
             state
          The Ekip Touch/Hi-Touch can be customized with the protection functions required.
            I4
                t4

          t     Extremely Inverse I I  L – Overload (L - ANSI 49)
                Very Inverse  This function is used for protection against overloads. It allows the setting of the trip threshold, trip
                Standard Inverse
          t t t  100% 200%  8 time and pre-alarm threshold. Three different types of trip curves are available:
            50% 150%              2
                 L         1.  t = k/l  with an inverse long time;
               I3 I7       2.  IDMT in accordance with IEC 60255-151 for coordination with medium voltage protection, available
                    S
                       I     according to Standard Inverse (SI), Very Inverse (VI) and Extremely Inverse (EI) curves;
                     t7  I  3.  With a t = k/l  curve for better coordination with upstream circuit-breakers or fuses.
                                        4
                       I I I
          t
                           S – Time-delayed overcurrent (S - ANSI 51 & 50TD)
          t t t  steady  U8
                            UV
          t  state  start-up  This function is used to protect against selective short-circuits. If necessary, it can be disabled, or if
                           needed, only the trip can be excluded keeping the alarm indication, to be used in installations where
            I2 I4 t8       continuity of service is required. With a constant trip time (t = k), or constant specific let through
               I7
                t2 t4  V   energy (t = k/l ).
                                       2
                     t7  I I
          t            I I
                           I – Short-circuit
             100% 200%
          t t t t  50% 150%  U9  This function is used for instantaneous protection against short-circuits. The trip threshold is
          t  steady  L      OV
             I1
             state  I3  t1 start-up  adjustable and, if needed, the protection can be disabled.
               I7   S t8 t9
                       V
                       I
                     t7
                       I I I
          t            I I
          t t              G - Ground fault
                            UF
                   f12
          t t  steady  start-up  This function protects against earth faults. The trip threshold and trip time are adjustable. When
             state 200%
             100%
            50% 150%
                 L         needed, the protection can be disabled.
             I2 I4 t12
             t12
                t2 t4  S  f
                       I I
          t            I I
                       I
          t t t  100% 200% f13  Neutral protection
                            OF
             I1
          t  50% 150%  L   This function is used to adjust the setting provided from protections L, S and I on the Neutral pole with  a
               I3  t1
                    t13    control factor which is different from the other phases. It is available with values at 50%, 100%, 150% or
                    S
            I4         f   200% of the phase currents. It can be disabled if necessary.
                t4     I
                       I I I
                    mean I
          t
                            voltage unbalance
          t t        U14   2I - Second protection against instantaneous overcurrent
                           This function protects against the instantaneous short-circuit (e.g. I protection) and it is enabled with
             I2
             I4  I3        an activation event (or command), that can be programmed by the user. It can be activated for different
                t2
            U1  U2  U3
                t4         uses in three ways:
                       I   •  locally, directly on the Ekip display unit
                V1     I I  •  locally, with a smartphone with the EPiC app via Bluetooth
                           •  locally, with a PC with the Ekip Connect program
          t t               senso ciclico
          t  I1            •  remotely, via any Ekip Com module connected to the circuit-breaker
                 t1        •  remotely, via a switch wired through an Ekip Signalling module.
               I3
            V3       V2    When active, the Ekip display unit will show a confirmation of the activation and a red LED alarm will
            I2             flash on the diagnosis bar. Moreover, the second instantaneous tripping curve is designed to mitigate
                t2
                       I I  against arc flashes (also referred to as RELT - Reduced Energy Let-Through).   This protection can be
                       I   adjusted from 1.5 to 15 xIn with a maximum setting of 18kA. Easy activation and I/O assignment, inclu-
                           ding positive feedback, can be established using the RELT Ekip Signaling 2k-3 module.
          t
          t
             I1
             I2  t1
                t2
                       I
                       I
          t
             I1
                 t1
                       I