Page 89 - SACE Tmax XT - Catalogue
P. 89

PROTECTION TRIP UNITS                                                            3/55



















                                                                                                                       03

          ABB Code  ANSI Code Function                Threshold Range      Trip Time
          RP        32R     Reverse active power      ± 10%                The better of the two data:
                                                                           ± 10% or ± 100ms (for t11<5s) / ± 100ms (for t11 ≥ 5s)
          D         68      Directional overcurrent   ± 7% I ≤ 6 x In      If t7 ≤ 200 ms : +/-20 ms
                                                      ± 10% I ≥ 6 x In     If 200ms < t7 ≤ 400 ms : 10%
                                                                           If t7 > 400 ms : 40 ms
          RQ        40/32R  Loss of field or reverse reactive   ± 10%      The better of the two data:
                            power                                          ± 10% or ± 100ms (for t24<5s) / ± 100ms (for t24 ≥ 5s)
          OQ        320F    Reactive overpower        ± 10%                The better of the two data:
                                                                           ± 10% or ± 100ms (for t27<5s) / ± 100ms (for t27 ≥ 5s)
          OP        320F    Active overpower          ± 10%                The better of the two data:
                                                                           ± 10% or ± 100ms (for t26<5s) / ± 100ms (for t26 ≥ 5s)
          UP        32LF    Active underpower         ± 10%                The better of the two data:
                                                                           ± 10% or ± 100ms (for t23<5s) / ± 100ms (for t23 ≥ 5s)
          ROCOF     81R     Rate of change of frequency  10% (20% when "0,4Hz/s" is   The better of the two data:
                                                      set)                 ± 20% or ± 200ms
          L (Motor          Motor protection overload
          Protection)       According 60947-4-1
          R         51LR    Rotor blockage  - Jam     Ij = 2…10 x I1       tj = 1…10 s
                    51LR    Rotor blockage - Stall    Is = 1…10 x I1       ts = 2…10 s
          U                 Phase lack and/or unbalance  ± 10%             The better of the two data:
                                                                           ± 10% or ± 40ms (for tu<5s) / ± 40ms (for tu ≥ 5s)
          Uc        37      Undercurrent              ± 10%                The better of the two data:
                                                                           ± 10% or ± 40ms (for tuc<5s) / ± 40ms (for tuc ≥ 5s)
          Protection with additional modules
          SC        25      Synchrocheck (Live busbars)  10%
          Synchrocheck
                            Synchrocheck  (Live. Dead busbars)  10%
          Gext      50GTD   Earth fault               ± 7%                 The better of the two data:
                                                                           ± 10% or ± 40ms
                    51G     Earth fault               ± 7%                 ± 15%
                    51G     Earth fault
          MDGF (2)          Earth fault               ± 7%                 The highest between 15% or 15ms
          Rc        64 50N TD  Residual current /     - 20% ÷ 0%           140ms @   (max trip time)
                    87N     Differential ground fault                      950ms @   (max trip time)
          (1) 2I Trip time with Vaux only:
          - ≤ 3ms when the fault current exceeds18kA;
          - ≤ 7ms (three-phase) or ≤9ms (single-phase) when the fault is greater than three times the 2I setting (I31);
          - ≤ 15ms when the fault is lower than three times the 2I setting (I31)
          (2) Available for XT7 only.
          The tolerances above apply to trip units already powered by the main circuit with current flowing in at least two phases or an auxiliary power supply.
          In all other cases the following tollerance values apply:

          ABB Code     Trip threshold       Trip time
          L            Trip between 1.05 and 1.2 x I1  ± 20%
          S            ± 10%                ± 20%
          I            ± 15%                ≤ 60ms
          G            ± 10%                20% (60ms when t4=inst)
          Other protection  ± 15%           ± 20%
   84   85   86   87   88   89   90   91   92   93   94