                      Configuration The  Circuit breaker-Configuration menu, allowing the presence of the  External neutral sensor to be
                                    activated, is available for the 3P CB (page 194).
                                    Activation of the configuration with External neutral (3P + N) enables:
                                     •  histograms of phase Ne in the Histograms page
                                     •  neutral current measurements
                                     •  submenu for configuring the Neutral protection (Neutral Protection)
                                     •  neutral current recording in the case of TRIP
                                    With 3P CB, the parameter is set by default as: 3P.


                     Line frequency Frequency adjustment is performed to set the installation frequency; the choice is between 50 Hz and
                                    60 Hz.
                                           NOTE: the measurements are taken on the basis of the set grid frequency: incorrect
                                           configuration of the parameter may lead to abnormal measurements and protection
                                    Ekip Touch is supplied with the parameter setting that suits the ordered configuration.


                           Modules The Modules menu provides various options:

                                     Parameter        Description                                         Default
                                                      The parameter defines the mode in which the parameters are
                                                      written in the unit:
                                                       • Local: parameter editing only via the display or service
                                                      connector
                                                       • Remote: parameter editing only remotely (Ekip Com modules)
                                     Local/Remote         NOTES:                                          Local
                                                            • the Remote mode requires the presence of auxiliary
                                                          power supply and Ekip Com modules, otherwise it disables
                                                          automatically
                                                            • However, the Local/Remote parameter can still be edited
                                                      in the Remote mode
                                                      The parameter enables communication between the Trip unit
                                                      and modules installed via terminal box or outside the unit to be
                                                      activated.
                                                      Correct communication between unit and modules is confirmed
                                                      by:
                                     Local bus                                                            Off
                                                       • population of the Modules menu with all the modules
                                                      connected
                                                       • Power Leds of the modules on and synchronized like the power
                                                      led of Ekip Touch
                                                       • absence of Local Bus alarm in the diagnosis bar
                                     Ekip Measuring   Menu with installation voltage parameters (page 114)
                                     -                Menu of every module connected and detected (from page 124)
                                                      Access to the LOCAL Switch On and RESET signaling functions
                                     Functions
                                                      (from page 72)