Page 119 - MCCB-XT2-XT4
P. 119
ABB | SACE Tmax XT
Customers Page Enabling and fields for editing the Customers page (5 information lines) that can be viewed on the display
of the unit (page 114).
Installation Date of installation of unit
Load Profile Time The counter indicates the time that has elapsed since the last reset of the energy measurements. It is
active and updated in the presence of at least one of the following: auxiliary supply or supply by Ekip T&P.
Led Alive The parameter enables the behavior of the Power led of the Trip unit and of all the connected modules to
be modified; if activated (Alive Mode on), the Power leds act in the following way:
• Ekip Touch: flashes at 0.5 Hz frequency
• Modules: if there are no communication errors, they synchronize with the led of Ekip Touch.
If deactivated, the Power leds on the respective devices come on with a steady light.
Open/Close Remote Direct The parameter controls 2 different command packages for remote opening and closing:
Command • Enabled: direct Open and Close commands valid.
• Disabled: direct commands not valid; in this case, remote opening and closing can still be obtained
using the programmable YC COMMAND and YO COMMAND functions and the Request circuit-
breaker opening and Request circuit-breaker closing commands.
Change Double Set of If activated, enables the set of parameters (Adaptive Protections) to be changed even when timing alarms
parameters always are in progress.
Disabled by default.
Repeat zone selectivity S/I/2I/ If Enabled, zone selectivity HW signals propagation logic applies in accordance with the table in the QT1
MCR/G HW technical application notes. 1SdC007100G0205
If Disabled, the HW selectivity signal is not propagated by Ekip Touch
Zone selectivity input The zone selectivity inputs and certain of the outputs can be configured in this section:
functions • Standard: input or output operation as per standard zone selectivity logic; all selectivity functions
are set as Standard. (1SdC007100G0205 or 1SdC007401G0201)
• Customized: the event that activates the zone selectivity input or output can be selected.
IMPORTANT: in the Customized configuration, the only zone selectivity activation event
is the one set and standard selectivity operation is therefore not active (changes should
only be made by expert technical personnel).
Glitch The commands of Glitches 16 to 23 activate the respective glitch registers, which can be used for
customizing programmable functions or output contacts.
117 | © 2022 ABB | 1SDH002031A1002 - ECN000212994 Ekip Touch - Settings | 2 - Additional settings