Page 120 - MCCB-XT2-XT4
P. 120
ABB | SACE Tmax XT
Ekip Touch - Test
1 - Test
Presentation The test area can be accessed on the display; the commands available in this area allow certain functions
of the Trip unit to be checked; details of all the commands available in the Test menu are given below
(page 30).
Ekip T&P with Ekip Connect has a Test Protections section where the presence of current or voltage alarm
signals can be simulated and times and trips can be checked.
Autotest The Autotest command starts an automatic sequence of the display and leds so as to enable their
operation to be checked.
The sequence comprises the following test phases:
1. Screen with message “www.abb.com”.
2. Gradual fade-out of the words on the display.
3. Lighting up, for one second, of the Warning and Alarm leds.
Trip Test Selection of the Trip test command accesses the dedicated page where the operator is asked to press the
iTEST key to confirm the test operation.
An open command is transmitted to the Trip coil of the CB when the key is released.
IMPORTANT:
• the open command is sent with the circuit-breaker closed and in the absence of current
• following a command, the user is responsible for checking the effective change in status
of the actuator and the information displayed: make sure that there are no alarms on the
diagnosis bar before performing the test
NOTE: to reset the TRIP signal, go back to the HOME page and press the iTEST key or
transmit a TRIP RESET command (via Ekip Connect or remotely)
Test CB Selection of the Test CB command accesses a submenu with the Open CB and Close CB commands
allowing the CB to be opened and closed via MOE-E.
Correct operation of the entire command system (Trip unit, Ekip Com or Ekip Micro I/O module, MOE-E)
is checked by opening and/or closing the circuit-breaker.
IMPORTANT:
• the open and close commands only function when the Trip unit is on and powered by an
auxiliary supply
• release operation is checked by the commands: the test does not detect faults in the
power supply, connection or command system
118 | © 2022 ABB | 1SDH002031A1002 - ECN000212994 Ekip Touch - Test | 1 - Test