Page 117 - MCCB-XT2-XT4
P. 117

ABB | SACE Tmax XT

                             MLRIU The MLRIU parameters are available with Ekip M Touch for the Motor Protections functions (page 63).
                                           NOTE: to ensure correct operation, check where applicable: presence and status of the
                                           outgoing connections, those towards the Trip unit of Ekip CI and the relative output contact
                                           (O61)
                                    Parameters
                                     Parameter    Description                                             Default
                                                  Allows the TRIP mode to be set (page 34):
                                                   • Heavy: in the event of a TRIP, it is controlled by the Trip coil of the CB
                                                   • Normal: contact O61 of the Ekip CI module is opened in the event of
                                                  a TRIP
                                                       NOTES:
                                     Open Mode                                                            Standard
                                                       • the TRIP for protections G or I always involves the Trip coil
                                                     command, regardless of the Open Mode configuration
                                                       • in the Normal mode, if the Trip unit detects the presence of
                                                     a fault even after the open command sent to O61, a command is
                                                  also sent to the Trip coil of the CB
                                     Autoreclosure   When Open Mode= Normal, allows re-closing of contact O61 to be
                                     Enabled      activated after a TRIP due to protection L (On)         Off
                                                  Allows the trip class of the motor to be selected from among: 5E, 10E,
                                     Motor Class                                                          30E
                                                  20E (page 63)
                                                  Defines the time waited, after the open command of contact O61,
                                     Contactor    before the fault is considered to be still present and action is taken   0,1
                                     Delay        by sending a command to the Trip coil of the CB. The value is given in
                                                  seconds and can be set within the range: 0.1 s to 1 s, in 0.1 s steps
                                                  Defines the time waited after the open command of contact O61,
                                     Autoreclosure
                                     Time         before this latter is closed. The value is given in seconds and can be set  60
                                                  within the range: 1 s to 1000 s, in 1 s steps






















































       115 | © 2022 ABB |  1SDH002031A1002 - ECN000212994                            Ekip Touch - Settings | 1 - Main settings