Page 118 - MCCB-XT2-XT4
P. 118
ABB | SACE Tmax XT
2 - Additional settings
Presentation Via the service connector (via Ekip Connect) or system bus communication, you can:
A description of the different functions is given below.
Programmable States There are sixteen independent programmable states identified by the letters A, B, C, D, E, F, G, H, I, L, M, N,
O, P, Q, R, offering different solutions for event control.
Each programmable status can have two values: True or False. There are also various configuration
parameters available:
• Trigger: event or combination of several status activation events (up to 24, in AND or OR logic
configuration).
• On Delay: status activation delay calculated from trigger presence onwards.
• Off Delay: status de-activation delay calculated from trigger absence onwards.
NOTE: the status activates if the trigger is present for longer than the On delay setting and
de-activates if the trigger is absent for longer than the Off delay setting
Figure 27
The statuses can be used with external module Ekip Signalling 10K, on Link Bus or with the programmable
functions, so as to convey the required signaling combination to the contacts.
TAG Name, User data Tags that can be programmed by the user to facilitate remote identification of units.
NOTE: the Name TAG and communication address form the identification used by Ekip
Connect for the connected devices
116 | © 2022 ABB | 1SDH002031A1002 - ECN000212994 Ekip Touch - Settings | 2 - Additional settings