Page 116 - MCCB-XT2-XT4
P. 116
ABB | SACE Tmax XT
Test Bus The parameter allows parameter editing via the service connector to be enabled/disabled, thereby
limiting the possibility of configuring all the options on the display (in the Local mode) or via modules
Ekip Com (in the Remote mode).
Disabling the parameter, Local mode and using the PIN allow security against undesired modification by
unauthorized persons to be increased.
NOTE: with Test Bus= Off, communication via service connector is still guaranteed (reading
enabled)
Ekip Touch is supplied with the parameter set to: On.
System The System menu provides various options:
Parameter Description Default
Date Setting the current date
Time Setting the current time
Language Setting the language in display menus English
PIN PIN setting (page 33) 00001
IMPORTANT: setting and checking Date and Time is important for all the recording
functions (trips or measurements); in the event of date and time glitches, reset and if
necessary replace the battery inside Ekip Touch (page 18).
View The View menu allows you to access the Customer Page configuration mode:
Parameter Description Default
Allows you to activate a supplementary information page, which can
be accessed by pressing the iTEST button twice from any page with a
Customer page Off
diagnosis bar. The information on the new page can be configured via
Ekip Connect (page 117)
Display contrast Allows the level of contrast of the LCD display of Ekip Touch to be adjusted.
Maintenance The parameter allows an alarm, concerning maintenance of the unit, to be enabled/disabled. (page 97).
Ekip Touch is supplied with the parameter set to: On.
Ekip Measuring Certain installation voltage parameters can be configured in this menu:
Parameter Description Default
Selects the rated voltage value selection mode:
Un Setting • Table: value editable in preset steps Table
Mode
• Volt: value editable within the range in 1 V steps
Defines rated voltage Un.
The value is given in absolute value (V), editable within the 100 V to
Rated voltage 400 V
690 V range in steps which depend on the Un Setting Mode parameter
setting.
Defines the power flow required for D protection (page 56); 2 options
can be selected :
Positive Power High →
flow • High → Low: the power flows from the low terminals to the high Low
ones (load connected low)
• Low → High: opposite power flow (load connected high)
When Un Setting Mode is set in Table, the values of the voltage parameters can be as follows:
Parameter Voltage values with adjustment in steps
100 V, 115 V, 120 V, 190 V, 208 V, 220 V, 230 V, 240 V, 277 V, 347 V, 380 V, 400
Rated voltage
V, 415 V, 440 V, 480 V, 500 V, 550 V, 600 V, 660 V, 690 V
114 | © 2022 ABB | 1SDH002031A1002 - ECN000212994 Ekip Touch - Settings | 1 - Main settings