ABB | SACE Tmax XT

                           Test Bus The parameter allows parameter editing via the service connector to be enabled/disabled, thereby
                                    limiting the possibility of configuring all the options on the display (in the Local mode) or via modules
                                    Ekip Com (in the Remote mode).
                                    Disabling the parameter, Local mode and using the PIN allow security against undesired modification by
                                    unauthorized persons to be increased.
                                           NOTE: with Test Bus= Off, communication via service connector is still guaranteed (reading
                                           enabled)
                                    Ekip Touch is supplied with the parameter set to: On.


                            System The System menu provides various options:
                                     Parameter    Description                                         Default
                                     Date         Setting the current date
                                     Time         Setting the current time
                                     Language     Setting the language in display menus               English
                                     PIN          PIN setting (page 33)                               00001

                                           IMPORTANT: setting and checking Date and Time is important for all the recording
                                           functions (trips or measurements); in the event of date and time glitches, reset and if
                                           necessary replace the battery inside Ekip Touch (page 18).



                              View The View menu allows you to access the Customer Page configuration mode:
                                     Parameter    Description                                             Default
                                                  Allows you to activate a supplementary information page, which can
                                                  be accessed by pressing the iTEST button twice from any page with a
                                     Customer page                                                        Off
                                                  diagnosis bar. The information on the new page can be configured via
                                                  Ekip Connect (page 117)



                    Display contrast Allows the level of contrast of the LCD display of Ekip Touch to be adjusted.



                       Maintenance The parameter allows an alarm, concerning maintenance of the unit, to be enabled/disabled. (page 97).
                                    Ekip Touch is supplied with the parameter set to: On.



                     Ekip Measuring Certain installation voltage parameters can be configured in this menu:
                                     Parameter    Description                                             Default
                                                  Selects the rated voltage value selection mode:
                                     Un Setting    • Table: value editable in preset steps                Table
                                     Mode
                                                   • Volt: value editable within the range in 1 V steps
                                                  Defines rated voltage Un.
                                                  The value is given in absolute value (V), editable within the 100 V to
                                     Rated voltage                                                        400 V
                                                  690 V range in steps which depend on the Un Setting Mode parameter
                                                  setting.
                                                  Defines the power flow required for D protection (page 56); 2 options
                                                  can be selected :
                                     Positive Power                                                       High  →
                                     flow          • High  → Low: the power flows from the low terminals to the high   Low
                                                  ones (load connected low)
                                                   • Low  → High: opposite power flow (load connected high)

                                    When Un Setting Mode is set in Table, the values of the voltage parameters can be as follows:
                                     Parameter          Voltage values with adjustment in steps
                                                        100 V, 115 V, 120 V, 190 V, 208 V, 220 V, 230 V, 240 V, 277 V, 347 V, 380 V, 400
                                     Rated voltage
                                                        V, 415 V, 440 V, 480 V, 500 V, 550 V, 600 V, 660 V, 690 V