Page 126 - MCCB-XT2-XT4
P. 126

ABB | SACE Tmax XT

       4 - Ekip Com Modbus RTU



                                    Ekip Com Modbus RTU is a communication accessory which allows Ekip Touch to be integrated into an RS-
                                    485 network with Modbus RTU communication protocol, remote supervision and monitoring functions,
                                    in two different modes, master and slave.
                                    You can perform the following operations remotely:
                                     •  read Ekip Touch measurements and information
                                     •  manage certain controls, including opening and closing the actuator (MOE-E)
                                     •  access information and parameters not available on the display
                                     •  If connected to a withdrawable version of the circuit-breaker, the allows the racked-in/racked-out
                                       status to be detected
                                           NOTE: the remote open and close commands of the circuit-breaker can only be executed if
                                           Ekip Touch is in the Remote configuration
                                    The System Interface document is available for mapping the module in its communication network. All the
                                    required communication and command details are listed in the document (page 121).
                                    Accessories Ekip Cartridge and Ekip Supply are required in order to connect Ekip Modbus RTU to Ekip
                                    Touch (page 122 ,123).


                            Models Two different modules compatible with the Modbus RTU protocol are available: Ekip Com Modbus RTU
                                    and Ekip Com Modbus RTU Redundant.
                                    The modules are identical in terms of characteristics and installation methods, except for: display menus,
                                    cabling and addresses for system communication, which are specific for each module.
                                           NOTE: if different indications are not given, the information in the next chapter is valid for
                                           both models
                                    The two modules can be connected at the same time to Ekip Touch so as to expand the potential of the
                                    unit (e.g. for applications where high grid reliability is required).
                                           IMPORTANT: each Ekip Touch can be fitted with only one module per type. The configuration
                                           with two modules of the same model is not allowed (example: two Ekip Com Modbus
                                           RTU Redundant)



                       Connections To connect the module to its communication network and for references about the terminals, please
                                    consult document  1SdM000068r0001; use Belden 3105A type cables or equivalent for the external
                                    cabling.
                                    To connect the module to Ekip Supply and Ekip Cartridge, please consult document 1SdH002009A1503.


                      Power supply Ekip Com Modbus RTU is supplied directly by the Ekip Supply module to which it is connected.
                                           NOTE: communication between Ekip Touch and the module is interrupted in the absence
                                           of auxiliary power supply





























       124 | © 2022 ABB |  1SDH002031A1002 - ECN000212994              External electronic accessories | 4 - Ekip Com Modbus RTU