Page 124 - MCCB-XT2-XT4
P. 124

ABB | SACE Tmax XT

       2 - Ekip Cartridge



                                    Ekip Cartridge is an external accessory. It can be installed on standard 35 mm DIN rail (DIN EN 50022 type
                                    TS 35x15 mm) and allows Ekip Touch to be connected to other external accessories:
                                     •  all cartridge modules (e.g.: Ekip Supply, Ekip Com, etc)
                                     •  contact for signaling racked-in/racked-out state, in the case of withdrawable CBs





                            Models The two different models available allow two or four modules to be connected, respectively.
                                           IMPORTANT: one of the modules must always be Ekip Supply



                       Connections Ekip Cartridge has two terminal boxes:














                                    Figure 28

                                     Connector  Description
                                                Terminal for connecting the racked-in/racked-out status contact (AUP).
                                                    NOTE: Ekip Cartridge is supplied by default with a jumper on the terminal
                                     1
                                                    To use the racked-in/racked-out status signal, remove the jumper in the
                                                    connector and connect the cables from the fixed part of the CB.
                                                Terminal for connecting Ekip Cartridge to Ekip Touch.
                                                A list and description of the Pins is given below:
                                                 • K2: Supply output for Ekip Touch (-)
                                     2
                                                 • K1: Supply output for Ekip Touch (+)
                                                 • W3: CAN Bus
                                                 • W4: CAN Bus

                                    Access to all the external connections is available in the respective modules, on the upper side of Ekip
                                    Cartridge.


                          Mounting To connect the module to Ekip Touch, please consult document 1SdH002009A1503.





























       122 | © 2022 ABB |  1SDH002031A1002 - ECN000212994                     External electronic accessories | 2 - Ekip Cartridge