Page 160 - MCCB-XT5
P. 160
Continued from the previous page ABB | SACE Tmax XT
Parameter Description Default
Permits (Enabled ARP) the periodic generation of a
Gratuitous ARP message, used by Ekip Connect to rapidly
Disable Gratuitous ARP ARP Enabled
find the modules via Ethernet scan without knowing the IP
address beforehand
Password protected Enables the writing operations performed via the network Standard
access to be protected by a password (Request password) mode
With access protected by enabled password, this is the
Password Modbus TCP Local access
password to use before each writing session .
(2)
(1) Enable IEEE 1588 and Enable SNTP client must not be enabled at the same time
(2) the parameter can only be changed via system bus in the remote configuration
Remote Link configurations Regarding the Link functions, the following further parameters are available:
Parameter Description Default
Link Actor (1÷15) IP address of each actor (from 1 to 15) 0.0.0.0
Configuration parameters of the configurable states:
• selection of actor (actor from 1 to 15) which activates the
Remote Programmable programmable status Actor 1
Status (A÷D) None
• event of the actor that determines change of
programmable status
Configuration parameters of the words:
Remote Status word • selection of actor (actor from 1 to 15) from which the None
(A÷D) word status is taken 1 global
• selection of the taken word
Active (Passive diagnosis) or deactivated (No diagnosis) No
Diagnostic
cabled selectivity diagnosis Diagnostic
Diagnostic check 30 s, 1 min, 10 min, 60 min diagnosis frequency intervals 30 seconds
timeout available, if activated
Configuration of hardware selectivity (Only HW) or
Zone Selectivity Type HW only
hardware and logic (Mixed)
Interactive mask for selecting selectivity to be sent also
Repeat Configuration
mask to the upper levels (even if not active in the programmed 0x0000
device)
Remote information Additional information can be accessed via the service connector (via Ekip Connect) or via a system bus
communication:
Information Description
HW and Boot version General module information
Flash CRC status and
result Information about the correctness of the SW in the module
Ekip Link status Signals Ethernet cable connection errors
SNTP Server Error Error in communication with SNTP server
SNTP Server State of synchronism with SNTP server
Synchronization
Valid with Master IEEE 1588= ON, notifies the presence (Slave or PTP
IEEE 1558 status Master Active) or absence (PTP Master but Passive) of a higher level
master
Remote Link information Regarding the Link functions, the following further parameters are available:
Information Description
Information about the state and inconsistency of HW and logic
Line Congruency detection
selectivity (state and type of selectivity inconsistent)
Remote Programmable Status Status (true/false) of remote programmable statuses A, B, C and D
Remote Status Word Value of remote programmable Words A, B, C, D
Logic Zone Selectivity Logic selectivity states (inputs and outputs)
158 | © 2022 ABB | 1SDH002039A1002 - ECN000212994 External electronic accessories | 11 - Ekip Link