Continued from the previous page                               ABB | SACE Tmax XT
                                     Parameter          Description                                    Default
                                                        Permits (Enabled ARP) the periodic generation of a
                                                        Gratuitous ARP message, used by Ekip Connect to rapidly
                                     Disable Gratuitous ARP                                            ARP Enabled
                                                        find the modules via Ethernet scan without knowing the IP
                                                        address beforehand
                                     Password protected   Enables the writing operations performed via the network  Standard
                                     access             to be protected by a password (Request password)  mode
                                                        With access protected by enabled password, this is the
                                     Password Modbus TCP                                               Local access
                                                        password to use before each writing session .
                                                                                            (2)
                                    (1)  Enable IEEE 1588 and Enable SNTP client must not be enabled at the same time
                                    (2)  the parameter can only be changed via system bus in the remote configuration


         Remote Link configurations Regarding the Link functions, the following further parameters are available:
                                     Parameter          Description                                    Default
                                     Link Actor (1÷15)  IP address of each actor (from 1 to 15)        0.0.0.0
                                                        Configuration parameters of the configurable states:
                                                         • selection of actor (actor from 1 to 15) which activates the
                                     Remote Programmable   programmable status                         Actor 1
                                     Status (A÷D)                                                      None
                                                         • event of the actor that determines change of
                                                        programmable status
                                                        Configuration parameters of the words:
                                     Remote Status word    • selection of actor (actor from 1 to 15) from which the   None
                                     (A÷D)              word status is taken                           1 global
                                                         • selection of the taken word
                                                        Active (Passive diagnosis) or deactivated (No diagnosis)   No
                                     Diagnostic
                                                        cabled selectivity diagnosis                   Diagnostic
                                     Diagnostic check   30 s, 1 min, 10 min, 60 min diagnosis frequency intervals   30 seconds
                                     timeout            available, if activated
                                                        Configuration of hardware selectivity (Only HW) or
                                     Zone Selectivity Type                                             HW only
                                                        hardware and logic (Mixed)
                                                        Interactive mask for selecting selectivity to be sent also
                                     Repeat Configuration
                                     mask               to the upper levels (even if not active in the programmed   0x0000
                                                        device)




                Remote information Additional information can be accessed via the service connector (via Ekip Connect) or via a system bus
                                    communication:
                                     Information        Description
                                     HW and Boot version  General module information
                                     Flash CRC status and
                                     result             Information about the correctness of the SW in the module
                                     Ekip Link status   Signals Ethernet cable connection errors
                                     SNTP Server Error  Error in communication with SNTP server
                                     SNTP Server        State of synchronism with SNTP server
                                     Synchronization
                                                        Valid with Master IEEE 1588= ON, notifies the presence (Slave or PTP
                                     IEEE 1558 status   Master Active) or absence (PTP Master but Passive) of a higher level
                                                        master




            Remote Link information Regarding the Link functions, the following further parameters are available:
                                     Information             Description
                                                             Information about the state and inconsistency of HW and logic
                                     Line Congruency detection
                                                             selectivity (state and type of selectivity inconsistent)
                                     Remote Programmable Status Status (true/false) of remote programmable statuses A, B, C and D
                                     Remote Status Word      Value of remote programmable Words A, B, C, D
                                     Logic Zone Selectivity  Logic selectivity states (inputs and outputs)