Page 158 - MCCB-XT5
P. 158

ABB | SACE Tmax XT

                    Zone selectivity With the Zone Selectivity function:
                                     •  the IP addresses entered refer to actors with the role of interlock with respect to the current role
                                     •  the protections for which selectivity must be actuated by setting a mask, must be selected for each
                                       interlock actor entered. Thus set, the function will now be indicated as logic in the following text so
                                       as to distinguish it from the standard function, now also indicated as hardware in the following text
                                     •  thus selected, the protections add to those of the hardware S, I, 2I, MCR, G, D-Backward and D-Forward
                                     •  hardware selectivity only, or both hardware and logic selectivity can be selected
                                     •  diagnosis can be set, for each interlock release, to ascertain whether there is consistency between
                                       the hardware and logic selectivity information
                                     •  a mask can be set for the purpose of identifying those protections whose received selectivity
                                       information must be re-transmitted, regardless of whether the actor is in the alarm status. The
                                       mask is only applicable to logic selectivity information
                                    For further details about the Zone Selectivity function with Ekip Link, please consult page 79.



                       Connections For references about the connection and terminals, please consult document 1SdM000005A1001; a cable
                                    of the Class 6 S/FTP type (Class 6 with double screening S/FTP) must be used for the communication
                                    bus.
                                    To connect the module to Ekip Supply and Ekip Cartridge, please consult document 1SdH002009A1503.


                      Power supply Ekip Link is supplied directly by the Ekip Supply module to which it is connected.
                                           NOTE: communication between Ekip Touch and the module is interrupted in the absence
                                           of auxiliary power supply



                          Interface the module has three signaling leds:

                                                             2                          1










                                    Figure 50

                                     LEDs           Description
                                                    Signals the on status and correct communication with Ekip Touch:
                                                     • off: module off
                                                     • on steady or flashing synchronized with the Power led of Ekip Touch: module
                                     Power
                                                    on and communication with Trip unit present.
                                                     • flashing not synchronized with the Power led of Ekip Touch (2 fast flashes
                                                    per second): module on and communication with Trip unit absent
                                                    Indicates the communication state:
                                     Link (1)        • off: incorrect connection, signal absent.
                                                     • on steady: connection correct
                                                    Indicates the communication state:
                                     Activity (2)    • off: no activity on line
                                                     • flashing: activity on line present (receiving and/or transmitting)



















       156 | © 2022 ABB |  1SDH002039A1002 - ECN000212994                        External electronic accessories | 11 - Ekip Link