Configurations via menu Local bus activation, which is essential for starting the communication between module and Ekip Touch,
is available in the Settings menu (page 35).
The following communication parameters can be configured if the module has been correctly detected by
Ekip Touch in the Settings-Modules menu:
Parameter Description Default
Defines whether the module has the dynamic (Off) or
Static IP address ON static (On) IP address. OFF
Se = On all the associated parameters are enabled
Static address IP address Enables the static IP to be selected 0.0.0.0
Static Network Mask Enables the subnet mask to be selected 0.0.0.0
When there are several subnets, enables the IP address of
Static Gateway address 0.0.0.0
the node to which the module is connected to be selected
Information in menu The following information will be available in the About-Modules menu if Ekip Touch has detected the
module correctly:
Information Description
SN and version Identifier and SW version of the module
Address of the module, assigned to the module by a DHCP server at the
time of connection to the network in the case of configuration with a
IP address dynamic IP, or can be set via the menu in the event of a static IP
NOTE: without a DHCP server, the module automatically adopts a
random IP address within the 169.254.xxx.xxx range
Subnet mask; identifies the method for recognizing the subnet to which
Network Mask the modules belong and enables modules to be searched for within a
defined set of recipients.
IP address of the node to which the module is connected, in the presence
Gateway address
of several subnets
Address assigned by ABB, with OUI (Organizationally Unique Identifier)
MAC address equal to ac:d3:64, which uniquely identifies the manufacturer of an
Ethernet device
Remote configurations Additional parameters can be accessed via the service connector (via Ekip Connect) or via a system bus
communication:
Parameter Description Default
Parameter for changing the configuration of the module
from Server Only to Client and Server and for integrating it
into an interactive data exchange network (see Ekip Com
Client/Server Server only
Hub on page 159).
IMPORTANT: if Client/Server, the module allows
data exchange like a normal Server function
Allows the IEEE 1588 protocol for distribution of the clock
Enable IEEE 1558 OFF
and synchronization signal to be enabled .
(1)
Enables the module to be set up as a master in the the
IEEE 1558 Master network segment to which it belongs (synchronization OFF
clock).
IEEE 1558 Delay Allows the data exchange mode between module and
mechanism master, either Peer-to-Peer or End-to-End, to be selected. End-to-End
Allows the SNTP protocol for distribution of the clock and
Enable client SNTP Off
synchronization signal to be enabled (1)
Allows the network server that supplies the SNTP to be
ANTP Server address 0.0.0.0
set.
Time zone Defines the time zone to be used for synchronism +00:00
Used to select whether daylight saving time is
Daylight Saving Time present (ON) or not (OFF) in the country to which the OFF
synchronization time refers
Continued on the next page
157 | © 2022 ABB | 1SDH002039A1002 - ECN000212994 External electronic accessories | 11 - Ekip Link