Page 161 - MCCB-XT5
P. 161
ABB | SACE Tmax XT
12 - Ekip Com Hub
Ekip Com Hub is a communication accessory that enables the data and measurements of Ekip Touch and
other devices connected to the same installation to be gathered and then made available on the server
through an Ethernet network.
The configuration of the module is available via Ekip Connect or with the System Interface document,
which contains all the details. (page 129).
The ports used by the module are:
Port Service Notes
67/udp 68/udp DHCP client DHCP client enabled alternatively as Static address = On
443/tcp HTTPS Always active when module is enabled
123/udp SNTP Active with SNTP client enabled
53/udp DNS Always active
The Ekip Com Modbus RTU and Ekip Com Modbus TCP modules can be configured to support Ekip Com
Hub in the collection of data to send to Cloud. See Getting Started 1SdC200063B0201.
Accessories Ekip Cartridge and Ekip Supply are required in order to connect Ekip Com Hub to Ekip Touch
(page 130, 131).
If connected to a withdrawable version of the circuit-breaker, it is possible to detect the racked-in/racked-
out status
Safety and cyber security The module uses the HTTPS protocol and can be connected to the Internet
IMPORTANT:
• it is the customer's sole responsibility to provide and continuously ensure a secure
connection between the module and customer network or any other network (as the case
may be). The plant manager must establish and maintain appropriate measures (such as
but not limited to the installation of firewalls, application of authentication measures,
encryption of data, installation of antivirus programs, etc.) to protect the product,
the network, the customer system and interface against any kind of security breaches,
unauthorized access, interference, intrusion, loss and/or theft of data or information.
ABB and its affiliates are not liable for damages and/or losses related to such security
breaches, unauthorized accesses, interference, intrusion, loss and/or theft of data or
information.
Connections For references about the connection and terminals, please consult document 1SdM000005A1001; a cable
of the Class 6 S/FTP type (Class 6 with double screening S/FTP) must be used for the communication
bus.
To connect the module to Ekip Supply and Ekip Cartridge, please consult document 1SdH002009A1503.
Power supply Ekip Com Hub is supplied directly by the Ekip Supply module to which it is connected.
NOTE: communication between Ekip Touch and the module is interrupted in the absence
of auxiliary power supply
159 | © 2022 ABB | 1SDH002039A1002 - ECN000212994 External electronic accessories | 12 - Ekip Com Hub