Page 74 - MCCB-XT5
P. 74

ABB | SACE Tmax XT

                     PTC Protection Function
                                    PTC protects the motor against overtemperatures.
                                    The Trip unit receives the alarm from the Ekip CI module to which a thermocouple can be connected for
                                    the purpose of monitoring the temperature of the motor: the protection sends a TRIP command if the
                                    temperature measured exceeds 120 °C for more than one second.
                                    Parameters

                                     Parameter    Description                                         Default
                                                  Activates/deactivates the protection and its availability in the
                                     Enable                                                           OFF
                                                  parameters menu
                                                  Activates/deactivates transmission of the open command: if
                                     Trip Enable  disabled, the alarm and exceedance of protection time are only   OFF
                                                  managed as information











































































       72 | © 2022 ABB |  1SDH002039A1002 - ECN000212994                                 Protections | 9 - Motor protections