       10 - Additional protections and functions



                       Introduction Some protections have additional functions which extend their characteristics and performance:
                                     Name           Type of protection                             Page
                                     Thermal Memory  overheating of the cables                     73
                                                    management of trip commands in a network of
                                     Zone selectivity                                              73
                                                    circuit-breakers
                                                    blocking of protection on the basis of programmable
                                     Blocks                                                        76
                                                    events
                                     Startup        different thresholds on the basis of monitoring thresholds 76
                                     Current thresholds Current control with programmable thresholds  77
                                     Programmable   Programmable commands with trip unit  events or   78
                                     Commands       statuses

                                    The presence of Ekip Synchrocheck allows the protections of the module to be activated (page 78)


         Thermal Memory Protection The function, which is available for L and S protections, allows overheating in the cables connected to
                                    the circuit-breaker to be prevented: in the case of trips within brief intervals, the unit considers the time
                                    between commands and the entity of the faults so as to reduce opening time.
                                           IMPORTANT: for the S protection the function can be activated if the selected curve is
                                           time-dependent.

                                           NOTE: the function also reduces the trip time in the case of overloads which have not
                                           led to the open command (longer than 100 ms)



              S, S2, I, 2I, MCR, G zone  The function, which can be activated for S, S2, I, 2I, MCR and G protections (if available and enabled),
               selectivity Protection allows several devices belonging to the same installation (including Ekip Touch) to be interconnected,
                                    so as to handle trip commands in the best possible way in the case of S, S2, I, 2I, MCR and G protections.
                                    The function allows the devices to be coordinated so that, if a fault occurs:
                                     •  the device nearest to the fault trips
                                     •  the other devices are blocked for a programmable time
                                           NOTE: connection can be made between ABB devices that have the zone selectivity function

                                    Characteristics
                                    Ekip Touch has five selectivity connections, located on the rear connectors of the CB:
                                     Name       Type       Description                       Connection
                                                           S, S2, I, 2I and MCR protection selecitivity  From devices on the load
                                     Szi        Input
                                                           input                            side
                                                           S, S2, I, 2I and MCR protection selecitivity  To devices on the supply
                                     Szo        Output
                                                           output                           side
                                                                                            From devices on the load
                                     Gzi        Input      G protection selectivity input
                                                                                            side
                                                                                            To devices on the supply
                                     Gzo        Output     G protection selectivity output
                                                                                            side
                                                           Common connection of selectivity   The entire selectivity
                                     Szc        Common
                                                           network                          network


                                                                                                Continued on the next page
















       73 | © 2022 ABB |  1SDH002039A1002 - ECN000212994                  Protections | 10 - Additional protections and functions