Page 177 - B_ELSB_Cat_2022_01_MCBs
P. 177

1
                                                                                                            1/177



          —
          MCBs technical details
          Coordination tables: selectivity




          Discrimination of S750 DR with respect to downstream MCB S200 / S400 compared to fuse protection
          MCBs
                                                                                               S 200 /
                                                                                               S 400
                    supply side:     S 750 DR                               fuse
          final     Char.            E / K                                  gG
          circuit:
                          I [kA]     25
                          cu
                                 I  [A]  16  20  25  32  40  50  63  80  100  16  20  25  35  40  50  63  80 100
                                 n
          S 200     B, C  6       ≤ 2  10  10  10  10  10  10  10  10  10    0.3  0.7  1.2  4.6  5  10  10  10  10
          S 400 E
                                   3  10  10  10  10  10  10  10  10  10     0.3  0.7  1.2  4.6  5  10  10  10  10
                                   4  10  10  10  10  10  10  10  10  10     0.3  0.6  0.9  2.8  3.5  6  10  10  10
                                   6  10  10  10  10  10  10  10  10  10     0.2  0.5  0.8  2  2.5  3.3  5.5  10  10
                                   8  10  10  10  10  10  10  10  10  10             0.7  1.5  2  2.5  3.5  5  6
                                  10  10  10  10  10  10  10  10  10  10             0.7  1.5  2  2.5  3.5  5  6
                                  13  10  10  10  10  10  10  10  10  10             0.7  1.5  2  2.5  3.5  5  6
                                  16      10  10  10  10  10  10  10  10                 1.3  1.4  2  2.9  4.1  6
                                  20          10  10  10  10  10  10  10                     0.7  1.8  2.6  3.5  5
                                  25              10  10  10  10  10  10                     0.7  1.8  2.6  3.5  5
                                  32                  10  10  10  10  10                             2.2  3   4
                                  40                      10  10  10  10                             2.2  3   4
                                  50                          10  10  10                                     3.5
                                  63                              10  10                                     3.5
                          Limited overload selectivity





          Discrimination of S750 DR with respect to downstream MCB S200 / S400 compared to fuse protection
          MCBs

                                                                                               S 200 /
                                                                                               S 400
                    supply side:     S 750 DR                               fuse
          final     Char.            E / K                                  gG
          circuit:
                          I [kA]     25
                          cu
                                 I  [A]  16  20  25  32  40  50  63  80  100  16  20  25  35  40  50  63  80 100
                                 n
          S 200     K     6       ≤ 2  10  10  10  10  10  10  10  10  10    0.3  1.2  4  6   10  10  10  10  10
          S 400 E
                                   3  10  10  10  10  10  10  10  10  10     0.3  0.7  1.2  4.6  5  10  10  10  10
                                   4  10  10  10  10  10  10  10  10  10     0.3  0.6  0.9  2.8  3.5  6  10  10  10
                                   6  10  10  10  10  10  10  10  10  10             0.7  1.7  2.5  3  5.9  9  10
                                   8  10  10  10  10  10  10  10  10  10             0.4  0.8  1  1.7  2.5  4  6
                                  10  10  10  10  10  10  10  10  10  10             0.4  0.8  1  1.7  2.5  4  6
                                  16      10  10  10  10  10  10  10  10                 0.7  0.9  1.2  2.2  3.1  4.6
                                  20          10  10  10  10  10  10  10                     0.7  1.1  1.7  2.6  3.5
                                  25              10  10  10  10  10  10                     0.7  1.1  1.7  2.6  3.5
                                  32                  10  10  10  10  10                             1.5  2.2  3.5
                                  40                      10  10  10  10                             1.5  2.2  3.5
                                  50                          10  10  10                                     2.2
                                  63                              10  10                                     2.2

                          Limited overload selectivity
   172   173   174   175   176   177   178   179   180   181   182