Page 179 - B_ELSB_Cat_2022_01_MCBs
P. 179

1
                                                                                                            1/179



          —
          MCBs technical details
          Coordination tables: selectivity




          Discrimination of S750 DR with respect to downstream MCB S200M / S400M compared to fuse protection
          MCBs
                                                                                               S 200
                                                                                               S 200 M
                    supply side:     S 750 DR                               fuse
          final     Char.            E / K                                  gG
          circuit:
                          I [kA]     25
                          cu
                                 I  [A]  16  20  25  32  40  50  63  80  100  16  20  25  35  40  50  63  80 100
                                 n
          S200M     B, C  10      ≤ 2  15  15  15  15  15  15  15  15  15     1  1.2  4   10  10  15  15  15  15
          S400M
                                   3  15  15  15  15  15  15  15  15  15     0.3  0.7  1.2  4.6  5  15  15  15  15
                                   4  15  15  15  15  15  15  15  15  15     0.3  0.6  0.9  2.8  3.5  6  15  15  15
                                   6  15  15  15  15  15  15  15  15  15     0.2  0.5  0.8  2  2.5  3.3  5.5  15  15
                                   8  15  15  15  15  15  15  15  15  15             0.7  1.5  2  2.5  3.5  5  6
                                  10  15  15  15  15  15  15  15  15  15             0.7  1.5  2  2.5  3.5  5  6
                                  13  15  15  15  15  15  15  15  15  15             0.7  1.5  2  2.5  3.5  5  6
                                  16      15  15  15  15  15  15  15  15                 1.3  1.4  2  2.9  4.1  6
                                  20          15  15  15  15  15  15  15                     0.7  1.8  2.6  3.5  5
                                  25              15  15  15  15  15  15                     0.7  1.8  2.6  3.5  5
                                  32                  15  15  15  15  15                             2.2  3   4
                                  40                      15  15  15  15                             2.2  3   4
                                  50                          15  15  15                                     3.5
                                  63                              15  15                                     3.5
                          Limited overload selectivity



          Discrimination of S750 DR with respect to downstream MCB S200M / S400M compared to fuse protection
          MCBs

                                                                                               S 200
                                                                                               S 200 M
                    supply side:     S 750 DR                               fuse
          final     Char.            E / K                                  gG
          circuit:
                          I [kA]     25
                          cu
                                 I  [A]  16  20  25  32  40  50  63  80  100  16  20  25  35  40  50  63  80 100
                                 n
          S200M     K     10      ≤ 2  15  15  15  15  15  15  15  15  15    0.3  1.2  4  10  10  15  15  15  15
          S400M
                                   3  15  15  15  15  15  15  15  15  15     0.3  0.7  1.2  4.6  5  15  15  15  15
                                   4  15  15  15  15  15  15  15  15  15     0.3  0.6  0.9  2.8  3.5  6  15  15  15
                                   6  15  15  15  15  15  15  15  15  15             0.7  1.7  2.5  3  5.9  9  15
                                   8  15  15  15  15  15  15  15  15  15             0.4  0.8  1  1.7  2.5  4  6
                                  10  15  15  15  15  15  15  15  15  15             0.4  0.8  1  1.7  2.5  4  6
                                  16      15  15  15  15  15  15  15  15                 0.7  0.9  1.2  2.2  3.1  4.6
                                  20          15  15  15  15  15  15  15                     0.7  1.1  1.7  2.6  3.5
                                  25              15  15  15  15  15  15                     0.7  1.1  1.7  2.6  3.5
                                  32                  15  15  15  15  15                             1.5  2.2  3.5
                                  40                      15  15  15  15                             1.5  2.2  3.5
                                  50                          15  15  15                                     2.2
                                  63                              15  15                                     2.2

                          Limited overload selectivity