Page 179 - B_ELSB_Cat_2022_01_MCBs
P. 179
1
1/179
—
MCBs technical details
Coordination tables: selectivity
Discrimination of S750 DR with respect to downstream MCB S200M / S400M compared to fuse protection
MCBs
S 200
S 200 M
supply side: S 750 DR fuse
final Char. E / K gG
circuit:
I [kA] 25
cu
I [A] 16 20 25 32 40 50 63 80 100 16 20 25 35 40 50 63 80 100
n
S200M B, C 10 ≤ 2 15 15 15 15 15 15 15 15 15 1 1.2 4 10 10 15 15 15 15
S400M
3 15 15 15 15 15 15 15 15 15 0.3 0.7 1.2 4.6 5 15 15 15 15
4 15 15 15 15 15 15 15 15 15 0.3 0.6 0.9 2.8 3.5 6 15 15 15
6 15 15 15 15 15 15 15 15 15 0.2 0.5 0.8 2 2.5 3.3 5.5 15 15
8 15 15 15 15 15 15 15 15 15 0.7 1.5 2 2.5 3.5 5 6
10 15 15 15 15 15 15 15 15 15 0.7 1.5 2 2.5 3.5 5 6
13 15 15 15 15 15 15 15 15 15 0.7 1.5 2 2.5 3.5 5 6
16 15 15 15 15 15 15 15 15 1.3 1.4 2 2.9 4.1 6
20 15 15 15 15 15 15 15 0.7 1.8 2.6 3.5 5
25 15 15 15 15 15 15 0.7 1.8 2.6 3.5 5
32 15 15 15 15 15 2.2 3 4
40 15 15 15 15 2.2 3 4
50 15 15 15 3.5
63 15 15 3.5
Limited overload selectivity
Discrimination of S750 DR with respect to downstream MCB S200M / S400M compared to fuse protection
MCBs
S 200
S 200 M
supply side: S 750 DR fuse
final Char. E / K gG
circuit:
I [kA] 25
cu
I [A] 16 20 25 32 40 50 63 80 100 16 20 25 35 40 50 63 80 100
n
S200M K 10 ≤ 2 15 15 15 15 15 15 15 15 15 0.3 1.2 4 10 10 15 15 15 15
S400M
3 15 15 15 15 15 15 15 15 15 0.3 0.7 1.2 4.6 5 15 15 15 15
4 15 15 15 15 15 15 15 15 15 0.3 0.6 0.9 2.8 3.5 6 15 15 15
6 15 15 15 15 15 15 15 15 15 0.7 1.7 2.5 3 5.9 9 15
8 15 15 15 15 15 15 15 15 15 0.4 0.8 1 1.7 2.5 4 6
10 15 15 15 15 15 15 15 15 15 0.4 0.8 1 1.7 2.5 4 6
16 15 15 15 15 15 15 15 15 0.7 0.9 1.2 2.2 3.1 4.6
20 15 15 15 15 15 15 15 0.7 1.1 1.7 2.6 3.5
25 15 15 15 15 15 15 0.7 1.1 1.7 2.6 3.5
32 15 15 15 15 15 1.5 2.2 3.5
40 15 15 15 15 1.5 2.2 3.5
50 15 15 15 2.2
63 15 15 2.2
Limited overload selectivity