Page 137 - 35_DS702_E_2014_Lightning_Protection_Guide
P. 137

Concrete
            Connection for the LPS,
            e.g. StSt (V4A, material
            No. AISI/ASTM 316 Ti)                            Wall / earth electrode bushing
                                                             Part No. 478 410
                   Soil

                                                            Main earthing busbar (MEB)
            Maximum ground water level                      Part No. 563 200



                                                                            Connecting clamp
                                                                            Part No. 308 025
             Cross unit
             Part No. 319 209               Tank sealing                            Foundation slab








                                               Functional equipotential bonding conductor  Blinding layer
                                        Corrosion-resistant ring earth electrode, StSt (V4A) (e.g. material No. AISI/ASTM 316 Ti)
                                        Max. mesh size of the ring earth electrode of 10 m x 10 m

          Figure 5.5.2.19  Arrangement of the earth electrode in case of a “black tank” according to the German DIN 18014 standard





















          Figure 5.5.2.20  Ring earth electrode in case of perimeter insulation;   Figure 5.5.2.21  Detailed view of a ring earth electrode; source:
                    source: Company Mauermann                     Company Mauermann


          bridges and additionally protects the sealing from mechanical   on the earth resistance of foundation earth electrodes which
          damage (Figures 5.5.2.20 and 5.5.2.21).      are conventionally installed in the foundation slab. A resistivity
          The resistivity of the perimeter insulation boards is a decisive   of 5.4 ⋅ 10  Ωm is specified for e.g. polyurethane foam with a
                                                              12
                                                                    3
          factor when considering the effects of the perimeter insulation   density of 30 kg/m . The resistivity of concrete, in contrast, is


          136  LIGHTNING PROTECTION GUIDE                            www.dehn-international.com