Page 154 - 35_DS702_E_2014_Lightning_Protection_Guide
P. 154

The equation is an approximation for spatial structures and for   The distances of the down conductors are based on the class of
       n ≥ 4. The values of h and c are assumed to be up to 20 m at a   LPS (Table 6 of IEC 62305-3 (EN 62305-3)). A deviation of +/–
       distance of 3 m. If internal down conductors are installed, they   20 % is acceptable. Thus, the distance c defines the largest dis-
       should be considered in the number n.        tance between the symmetrically arranged down conductors.
       In case of flat-roofed structures, the partitioning coefficient k c
       is calculated as follows. A type B earth electrode arrangement   Detailed approach for determining the separation
       is a precondition in this case (Figure 5.6.9):  distance s
                                                    In addition to the possibilities described above for determining
                      1               c
                k =     + 0.1+ 0.2   3              the partitioning coefficient k c  and the separation distance s,
                 c   2n               h             a more detailed calculation method can be used. In case of
                                                    buildings with a meshed lightning protection system, the cur-
       where                                        rent is split evenly due to the high number of current paths
       h    is the distance or height between ring conductors  formed by conductors on the flat roof and down conductors.
       c    is the distance between a down conductor and the   This has a positive effect on the separation distance. If a roof-
            next down conductor                     mounted structure as shown in Figure 5.6.10 is installed on
       n    is the total number of down conductors  a building, the detailed calculation method allows to calculate


                                                                                    number
                                                                                    of down
                        c                                 s = k i  (k c1  ⋅ l 1  + k c2  ⋅ l 2  + ... + k cn  ⋅ l n )  conductors
                                                                                    n = 24
                                                                                    1/n = 0.042
                                                                          0.25  0.25  0.25
                                                                       0.5  B
                                                                     A              air-termination
                                                      0.042 0.0625 0.125  0.25      conductor
                                                                                    mesh size acc.
                                                                     factor k c1
                                                                                    to class of LPS
         l
                                                             1.0
              h                                            0.5                      down
                                                      0.12  0.25
                                                                                    conductor


       Figure 5.6.8  Gable roof with four down conductors  Determination of the shortest current path from
                                                          the point of strike to the earth-termination system


                                                            Even current distribution at the point of strike



                                                         The current is reduced by 50 % at any further junction

         h
                                                             If the current is < 1/n, further calculations
                                                               with  k cn  = 1/n must be performed
                      c
       Figure 5.6.9  Values of coefficient k c  in case of a meshed network   Figure 5.6.10  Values of coefficient k c  in case of a system consisting
               of air-termination conductors and a type B earthing   of several down conductors according Figure C.5 of
               arrangement                                    IEC 62305-3 (EN 62305-3)



            www.dehn-international.com                             LIGHTNING PROTECTION GUIDE  153
   149   150   151   152   153   154   155   156   157   158   159