Page 150 - 35_DS702_E_2014_Lightning_Protection_Guide
P. 150

5.5.7.5  Other anti-corrosion measures       trical installations in the structure requiring protection is not
       Connecting cables / terminal lugs between founda-  sufficient.
       tion earth electrodes and down conductors    Metal installations such as water, air-conditioning and elec-
       Galvanised steel connecting cables between foundation earth   tric lines form induction loops in the building where impulse
       electrodes and down conductors should be laid in concrete or   voltages are induced due to the quickly changing magnetic
                                                    lightning field. It must be prevented that these impulse volt-
       masonry until they are above the surface of the earth.  ages cause uncontrolled flashover which can also result in fire.
       If the connecting cables are led through the ground, terminal   Flashover on electric lines, for example, can cause enormous
                               2
       lugs with e.g. NYY cable, 1 x 16 mm  Cu, stainless steel (V4A),   damage to the installation and the connected loads. Figure
       or fixed earthing terminals must be used.    5.6.1 illustrates the principle of the separation distance.
       Earthing conductors installed in the masonry can also be led   In practice, it is often difficult to use the formula for calculating
       upwards without corrosion protection.        the separation distance:
                                                                        k
       Earth entries made of galvanised steel                     s = k  c  l [m]
       Earth entries made of galvanised steel must be protected        i  k m
       against corrosion over a distance of at least 0.3 m above and   where
       below the surface of the earth.              k i    depends on the class of LPS selected (induction factor)
       Generally, bituminous coatings are not sufficient. A moisture-  k c    depends on the geometric arrangement (partitioning
       proof sheath, e.g. butyl rubber strips, heat-shrinkable sleeves   coefficient)
       or preferably stainless steel, provides protection.
                                                    k m    depends on the material used in the point of proximity
       Buried connection points                           (material factor) and
       Cut surfaces and connection points in the ground must be de-
       signed so as to ensure that they have an equivalent corrosion
       resistance as the corrosion protection layer of the earth elec-
       trode material. Connection points in the ground must therefore
       be equipped with a suitable coating, e.g. wrapped with an an-
       ticorrosive tape.

                                                                                       s 1
       Corrosive waste                                             S1
       When filling ditches and pits where earth electrodes are in-
       stalled, pieces of slag and coal must not directly contact the
       earth electrode material.  The same applies to construction
       waste.

                                                                            s 2      s 2
       5.5.8  Materials and minimum dimensions of
            earth electrodes
       Table 5.5.8.1 illustrates the minimum cross-sections, configu-          l
       ration and materials of earth electrodes.                                  l 2


       5.6  Electrical isolation of the external
           lightning protection system –                             MDB
           Separation distance                                       MEB
       There is a risk of uncontrolled flashover between parts of the                   l 1  = l
       external lightning protection system and metal and electrical
       installations in the building if the distance between the air-
       termination system or down conductor and metal and elec-  Figure 5.6.1  Principle of the separation distance



            www.dehn-international.com                             LIGHTNING PROTECTION GUIDE  149
   145   146   147   148   149   150   151   152   153   154   155