6.1  Equipotential bonding for metal         Every building must be equipped with a protective equipoten-
           installations                            tial bonding system in accordance with the standards stated
                                                    above (Figure 6.1.1).
       Equipotential bonding according to IEC 60364-4-41   Supplementary  protective  equipotential  bonding  is intended
       (HD 60364-4-41) and IEC 60364-5-54 (HD 60364-5-54)  for those cases where the conditions for disconnection of sup-
       Equipotential bonding is required for all electrical consumer’s   ply cannot be met or for special areas which conform to the
       installations installed. Equipotential bonding according to the   IEC 60364 series Part 7.
       IEC 60364 series removes potential differences, in other words
       it prevents hazardous touch voltages, for example, between   Protective equipotential bonding
       the protective conductor of the low-voltage consumer’s instal-
       lation and metal water, gas and heating pipes.  The following extraneous conductive parts must be directly
       According to IEC 60364-4-41 (HD 60364-4-41), equipotential   integrated in the protective equipotential bonding system:
       bonding consists of  protective equipotential bonding   ¨  Protective bonding conductor in accordance with
       and  supplementary protective equipotential bond-  IEC 60364-4-41 (HD 60364-4-41) (in the future: earthing
       ing.                                            conductor)






               buried installation,   functionally isolated   (e.g. cathodically   protected tank)  metal element extend-   ing through the entire   building (e.g. lift rail)  telecommunications system equipotential bonding system   230/400 V  Main earthing busbar


                                                                              Foundation earth
                                       antenna  of the bathroom  kWh          electrode
                                                                              Connector
                                                                              Lightning current
                                                                              arrester
                                                                              Connecting clamp
                                                                              Pipe clamp
                                                                              Terminal lug /
                                                                              earthing conductor
                                                         to PEN               Isolating spark gap


                                      heating                   SEB




             insulating joint  gas  water  waste-                               distribution  network
                M

                                                                                information  technology  system
                            water



             M                                                              terminal lug for external
                                                                            lightning protection system
           foundation earth electrode /
           lightning protection earth electrode

       Figure 6.1.1  Principle of lightning equipotential bonding consisting of lightning and protective equipotential bonding