Figure 5.1.2.4   Building with photovoltaic system and sufficient    Figure 5.1.2.5   Antenna with air-termination rod and spacer
                   separation distance; source: Blitzschutz Wettingfeld,
                   Krefeld
          Air-termination rods for chimneys must be installed to ensure   termination systems are used and the air-termination rods are
          that the entire chimney is located in the protected volume. The   installed by means of spacers. The metal pipe must be con-
          protective angle method is used to dimension the air-termina-  nected to the equipotential bonding system.
          tion rods.
          If the chimney is brick-built or constructed with preformed sec-  The assembly to protect parabolic antennas is similar to that to
          tions, the air-termination rod can be directly mounted on the   protect chimneys with a metal pipe.
          chimney.
          If there is a metal pipe in the interior of the chimney, e.g. if   In the event of a direct lightning strike to antennas, partial
          an old building is renovated, the separation distance to this   lightning currents can enter the building to be protected via
          conductive part must be maintained. To this end, isolated air-  the shields of the coaxial cables and cause the interference










                   Roof conductor holder                    expansion piece      Bridging braid
                   of type FB2                                                   Part. No. 377 015
                   Part. No. 253 050
                                                                            flexible connection

                                                                              distance between the
                                                                              roof conductor holders
                                                                              of approx. 1 m


                   Roof conductor holder
                   of type FB
                   Part. No. 253 015



          Figure 5.1.3.1  Air-termination system on a flat roof