Page 78 - 35_DS702_E_2014_Lightning_Protection_Guide
P. 78

detail B




                                                                                      detail A



                                        evaluation: BLIDS – SIEMENS
                                             I = 20400 A                         residential building

       Figure 5.1.4.1  Types of metal roofs, e.g. roofs   Figure 5.1.4.2  Example of damage: Sheet metal
                with round standing seam


       IEC 62305-3 (EN 62305-3) lightning protection standard clear-
       ly illustrates the risk for metal roofs. Where an external light-      rolling sphere
                                                                              with a radius acc.
       ning protection system is required, the metal sheets must have         to class of LPS
       the minimum values stated in Table 5.1.1.5.     air-termination tip
       The thicknesses t are not relevant for roofing materials. Metal
       sheets with a thickness t’ may only be used as a natural air-
       termination system if puncture, overheating and melting is ac-
       cepted. The owner of the structure must agree to accept this
       type of roof damage since the roof will no longer be rainproof.

       If the owner does not accept damage to the roof in the event
       of a lightning strike, a separate air-termination system must
       be installed on a metal roof so that the rolling sphere (radius
       r according to the class of LPS) does not touch the metal roof
       (Figure 5.1.4.3).                            Figure 5.1.4.3  Air-termination system on a metal roof – Protection
                                                              against puncture
       In this case, an air-termination system with many air-termina-
       tion tips is recommended.                              Suitable for all classes of LPS
                                                         Distance of the     Height of the air-
       The heights of air-termination tips in Table 5.1.4.1 have prov-  horizontal conductors  termination tip *)
       en effective in practice, regardless of the class of LPS.
                                                              3 m                 0.15 m
       When fixing the conductors and air-termination tips, no holes   4 m        0.25 m
       may be drilled into the metal roof. A number of conductor hold-  5 m       0.35 m
       ers is available for the different types of metal roofs (round
       standing seam, standing seam, trapezoidal). Figure 5.1.4.4a   6 m          0.45 m
       shows adequate conductors for a metal roof with round stand-  *)  recommended values
       ing seam. If conductor holders with lightning current carrying
       clamp are used, an air-termination tip can be directly fixed.  Table 5.1.4.1  Lightning protection for metal roofs – Height of the
                                                              air-termination tips
       It must be observed that e.g. on a trapezoidal roof the con-
       ductor in the conductor holder located at the highest point   Figure 5.1.4.5 shows a conductor holder with fixed conduc-
       of the roof must be fixed, whereas the conductors in all other   tor routing and an air-termination tip on a trapezoidal roof.
       conductor holders must be routed loosely due to the length   To reliably prevent the ingress of moisture, the conductor hold-
       compensation resulting from the changes in temperature     er must be hooked into the fixing screw above the cover plate
       (Figure 5.1.4.4b).                           for the drill hole.



            www.dehn-international.com                              LIGHTNING PROTECTION GUIDE  77
   73   74   75   76   77   78   79   80   81   82   83