ABB ARC GUARD SYSTEM™ – TVOC-2 INSTALLATION AND MAINTENANCE GUIDE 27
4.2.3 Mounting TVOC-2-COM
Follow these steps to connect TvOC-2-COM module to the
Arc Monitor:
WARNING 1 1 Trip Error
Make sure that supply voltage is switched off!
2 1
Trip Error
1. 1 Remove the TvOC-2 HMI module from the Arc
Monitor by pressing on both sides on HMI and at
the same time. 2 Pull straight out from the Arc
Monitor.
1SFC170011M0201
INFORMATION Figure 21
Remove the HMI
The removed TvOC-2 HMI module can be
mounted on the door.
See Mounting the HMI on door on page 21. 04
2. 3 Place the TvOC-2-COM into the Arc Monitor.
Trip Error
3
1SFC170011M0201
Figure 22
Place TvOC-2-COM
3. 4 Cut the cable casing 10 millimeters.
5 Insert the cable into the contact on the top of 4 10 mm
the TvOC-2-COM 0.2…1.5 mm 2
0.2…1.5 mm 2
Trip Error
5 +(B) -(A) DGND
1SFC170011M0201
Figure 23
Fasten cable into the TvOC-2-COM