ABB  ARC GUARD SYSTEM™ – TVOC-2  INSTALLATION AND MAINTENANCE GUIDE                27




          4.2.3    Mounting TVOC-2-COM

          Follow these steps to connect TvOC-2-COM module to the
          Arc Monitor:
               WARNING                                                        1 1  Trip Error
               Make sure that supply voltage is switched off!
                                                                                  2      1
                                                                         Trip Error
          1.    1  Remove the TvOC-2 HMI module from the Arc
               Monitor by pressing on both sides on HMI and at
               the same time.   2  Pull straight out from the Arc
               Monitor.
                                                                                                    1SFC170011M0201
               INFORMATION                                   Figure 21
                                                             Remove the HMI
               The removed TvOC-2 HMI module can be
               mounted on the door.
               See Mounting the HMI on door on page 21.                                                               04



          2.    3  Place the TvOC-2-COM into the Arc Monitor.





                                                                             Trip Error

                                                                           3





                                                                                                    1SFC170011M0201
                                                             Figure 22
                                                             Place TvOC-2-COM


          3.    4  Cut the cable casing 10 millimeters.
                5  Insert the cable into the contact on the top of                        4  10 mm
               the TvOC-2-COM                                                                     0.2…1.5 mm 2

                                                                                                  0.2…1.5 mm 2

                                                                   Trip Error


                                                                                         5      +(B)  -(A) DGND



                                                                                                     1SFC170011M0201
                                                             Figure 23
                                                             Fasten cable into the TvOC-2-COM
   22   23   24   25   26   27   28   29   30   31   32