ABB  ARC GUARD SYSTEM™ – TVOC-2  INSTALLATION AND MAINTENANCE GUIDE                29




          4.2.5    Configurations


               WARNING
               Make sure that supply voltage is switched off!
                                                                    1 2 3 4 5 6 7 8
          Arc Monitor can be configured to trip selected breakers
          depending on which optical detector or CSU-2 is
          connected. This configuration is done with a DIP switch.

          DIP switches

          The DIP switches are located on the front left hand on the                                 1SFC170011M0201
          Arc Monitor. There are 8 DIP switches. Only DIP switches 1,   Figure 28
          2, 3, 4 and 6 are activated. As default all DIP switches are   DIP switches
          set to position 0. See Figure 28.
                                                                                                                      04
          Breaker trip

          The trip contacts are located on top of the Arc Monitor.
          See Figure 29.

          DIP switches 3 and 4 configure trip contacts, K4, K5 and
          K6. All detectors , X1, X2 and X3, operate the trip signal
          relays K2 and K3. Adjust the DIP switches to achive the
          desired breaker configuration K4, K5, K6. See Figure 29.
                                                                                                    1SFC170011M0201
                                                              Figure 29
                                                              Breaker trip

          DIP switches 3 and 4 to position 0
          DIP switches 3 and 4 in position 0 is the default state
          (factory settings).

          Any detector on X1, X2 or X3 operates trip contacts, K4, K5                           43 44  53 54  63 64
          and K6. See Figure 30.
                                                                  O  1 2 34 56 7 8              K4  K5  K6
                                                                  N                             Trip  Trip  Trip
                                                                                       X3
                                                                                       X2
                                                                                       X1




                                                                                                     1SFC170011M0201
                                                              Figure 30
                                                              DIP switches 3 and 4 to position 0

          DIP switch 3 in position 0, DIP switch 4 to position ON
          Set DIP switch 3 to position 0 and DIP switch 4 to                                   43 44  53 54  63 64
          position ON.                                             O  1 2 34 56 7 8             Trip  K5 Trip  K6 Trip
                                                                                                K4
                                                                   N
          •  Detectors X1 operate trip contact K4.                                     X3
                                                                                       X2
          •  Detectors X2 operate trip contact K5.                                     X1
          •  Detectors X3 operate trip contact K6.
                                                                            43 44  53 54  63 64  43 44  53 54  63 64
                                                                            K4  K5  K6          K4  K5  K6
                                                                            Trip  Trip  Trip    Trip  Trip  Trip
                                                                    X3                  X3
                                                                    X2                  X2
                                                                    X1                  X1
                                                                                                     1SFC170011M0201
                                                                                                         1M0201
                                                                                                     1SFC17001
                                                                                                     1SFC17001 1M0201
                                                              Figure 31
                                                              DIP switch 3 in position 0, DIP switch 4 to position ON
   24   25   26   27   28   29   30   31   32   33   34