Page 29 - Arc Guard System - TVOC-2
P. 29
ABB ARC GUARD SYSTEM™ – TVOC-2 INSTALLATION AND MAINTENANCE GUIDE 29
4.2.5 Configurations
WARNING
Make sure that supply voltage is switched off!
1 2 3 4 5 6 7 8
Arc Monitor can be configured to trip selected breakers
depending on which optical detector or CSU-2 is
connected. This configuration is done with a DIP switch.
DIP switches
The DIP switches are located on the front left hand on the 1SFC170011M0201
Arc Monitor. There are 8 DIP switches. Only DIP switches 1, Figure 28
2, 3, 4 and 6 are activated. As default all DIP switches are DIP switches
set to position 0. See Figure 28.
04
Breaker trip
The trip contacts are located on top of the Arc Monitor.
See Figure 29.
DIP switches 3 and 4 configure trip contacts, K4, K5 and
K6. All detectors , X1, X2 and X3, operate the trip signal
relays K2 and K3. Adjust the DIP switches to achive the
desired breaker configuration K4, K5, K6. See Figure 29.
1SFC170011M0201
Figure 29
Breaker trip
DIP switches 3 and 4 to position 0
DIP switches 3 and 4 in position 0 is the default state
(factory settings).
Any detector on X1, X2 or X3 operates trip contacts, K4, K5 43 44 53 54 63 64
and K6. See Figure 30.
O 1 2 34 56 7 8 K4 K5 K6
N Trip Trip Trip
X3
X2
X1
1SFC170011M0201
Figure 30
DIP switches 3 and 4 to position 0
DIP switch 3 in position 0, DIP switch 4 to position ON
Set DIP switch 3 to position 0 and DIP switch 4 to 43 44 53 54 63 64
position ON. O 1 2 34 56 7 8 Trip K5 Trip K6 Trip
K4
N
• Detectors X1 operate trip contact K4. X3
X2
• Detectors X2 operate trip contact K5. X1
• Detectors X3 operate trip contact K6.
43 44 53 54 63 64 43 44 53 54 63 64
K4 K5 K6 K4 K5 K6
Trip Trip Trip Trip Trip Trip
X3 X3
X2 X2
X1 X1
1SFC170011M0201
1M0201
1SFC17001
1SFC17001 1M0201
Figure 31
DIP switch 3 in position 0, DIP switch 4 to position ON