Page 26 - Arc Guard System - TVOC-2
P. 26

26               ABB  ARC GUARD SYSTEM™ – TVOC-2  INSTALLATION AND MAINTENANCE GUIDE




          Connect Power Supply. To connect the power supply of
          the TvOC-2 unit 1SFA664001R1001 and 1SFA664001R1003
          do the following steps:                                            2.5x0.6    6
                                                                                         0.2 ... 2.5 mm 2  PE A1 A2 L1
                                                                                                   N
          1.   Connect wires for power supply, use a torque of         0.5 Nm            0.2 ... 2.5 mm 2
               0.5 Nm.
          2.   Use screwdriver 2.5 x 0.6 mm (0.98 x 0.23 inches).
          3.   Cable area 0.2 - 2.5 mm² (0.078 x 0.98 inch²).
                                                                  Trip Error
          4.   Connect the cable for power supply 100-240v AC /
               100-250v DC. See Figure 19.

               For 1SFA664001R1002 and 1SFA664001R1004
               connect the cable for power supply 24-48v DC.                                         1SFC170011M0201
               The unit has dual power supplies (A1, A3) for   Figure 19
               redundancy with a common minus (A2). The       Connecting power supply
               supplies can be used separately. See Figure 20.
                                                                                         2.5x0.6   7
               WARNING                                                                               0.2 ... 2.5 mm 2
   04
                                                                                    0.5 Nm           0.2 ... 2.5 mm 2
               Always connect PE to Protective Earth!
                                                                                         A1 A3 +  A2 -  PE
                                                                                         +
                                                                                          28-48V DC

                                                                   Trip Error
                                                                                     1SFA6641001R1002



                                                                                                     1SFC170011M0201
                                                              Figure 20
                                                              Dual power supply
   21   22   23   24   25   26   27   28   29   30   31