ABB  ARC GUARD SYSTEM™ – TVOC-2  INSTALLATION AND MAINTENANCE GUIDE                23




          Example 3, Mounting in a circuit breaker cubicle
          In a circuit breaker cubicle there is a risk of detecting
          breaking arcs unintentionally, if the detector is placed
          above the busbars. In such a cubicle it is better to place
          the detector at the bottom. See Figure 9.

          •  Use the same mounting bracket as for top mounting
            but the bend is turned upwards and the detector
            placed on the upper side.
          •  Drill a hole 20 mm (0.79 inches) in front of the busbars,
            where the detector can be located.
                                                                                                     1SFC170011M0201
          If many cables are connected to the terminals on the lower   Figure 9
                                                              Place the detector at the bottom
          side of the circuit breaker, the arc monitoring should
          have an additional detector located just behind the front
          protective sheet.  See Figure 10.                                                                           04
          Attach the detector directly to the bottom side of the
          bracket of the protective cover with a cable strap.


          Example 4, Mounting on a wall
          Attach the lens from the front and pull the cable from the
          back of the panel and fasten from the front of the panel or
          Install the lens through the panel and fasten on the back
          of the panel The minimum diameter of the hole should be
          9.85 mm. See Figure 11.                                                                    1SFC170011M0201
                                                              Figure 10
                                                              Additional detector located just behind the protective sheet
          Connecting optical detectors

               WARNING
               Make sure that supply voltage is switched off!

          Follow this steps below to connect the optical detectors
          to the Arc Monitor.
          1.    1  Remove the protection plug or the dummy plug.
               WARNING
               Only remove protection plug from connection
               to use. Protection plugs are needed to protect
               the detector inputs from dust and light.

                                                              Figure 11
               WARNING                                        Place the detector at the bottom
               For the E6-S extension unit, the dummy plugs
               (TvOC-2-PP2) connected at delivery, are also
               used to maintain functionality of the unit.
               Removing the dummy plugs will not only
               allow for dirt and dust to enter but will trigger
               warnings on the HMI for damaged detectors.

          2  Connect optical detectors to lower side of Arc Monitor.
          Detector inputs are X1:1-10 (for Extension 1, X2:1-10 and
          Extension 2, X3:1-10)                                                           2
                                                                     1

                                                                                                     1SFC170011M0201
                                                              Figure 12
                                                              Connect the detector cable
   18   19   20   21   22   23   24   25   26   27   28