Page 555 - Din prodcuts 2020
P. 555

5/111




          —
          Protection and safety
          Data & signal protection
          OVR E Series


          OVR E Series - Technical specification
          Electrical specification      OVR 06E        OVR 15E       OVR 30E       OVR 50E        OVR 110E
          ABB order code                7TCA085400R0346 7TCA085400R0350 7TCA085400R0353 7TCA085400R0354 7TCA085400R0348  5
          Nominal voltage  (1)          6 V            15 V          30 V          50 V           110 V
          Maximum working voltage Uc (RMS/DC)  (2)  5 V/7.79 V   11 V/16.7 V   25 V/36.7 V   40 V/56.7 V   93 V/132 V
          Current rating (signal)       1.25 A
          In-line resistance (per line ±10%)  1.0 Ω
          Bandwidth (-3 dB 50 Ω system)  45 MHz
          Transient specification       OVR 06E         OVR 15E      OVR 30E       OVR 50E        OVR 110E
          Let-through voltage (all conductors)   Up
                                   (3)
          C2 test 4 kV 1.2/50 μs, 2 kA 8/20 μs to    36.0 V   39.0 V   60.0 V      86.0 V         180 V
          BS EN/EN/IEC 61643-21
          C1 test 1 kV, 1.2/50 μs, 0.5 kA 8/20 μs to   26.2 V   28.0 V   49.0 V    73.5 V         170 V
          BS EN/EN/IEC 61643-21
          B2 test 4 kV 10/700 μs to BS EN/EN/IEC   16.0 V   25.5 V   43.5 V        65.0 V         160 V
          61643-21
          5 kV, 10/700 μs  (4)          17.0 V         26.2 V        44.3 V        65.8 V         165 V
          Maximum surge current
          D1 test 10/350 μs   – Per signal wire  2.5 kA
          to BS EN/EN/IEC
          61643-21       – Per pair     5 kA
          8/20 μs to ITU-T    – Per signal wire  10 kA
          K.45:2003, IEEE    – Per pair  20 kA
          C62.41.2:2002
          Mechanical specification      OVR 06E        OVR 15E       OVR 30E       OVR 50E        OVR 110E
          Temperature range             -40 to +80 °C
          Connection type               Screw terminal - maximum torque 0.5 Nm
          Conductor size (stranded)     2.5 mm 2
          Earth connection              M6 stud
          Case material                 FR Polymer UL-94 V-0
          Weight         – Unit         0.08 kg
                         – Packaged (per 10)  0.85 kg
          Dimensions                    See diagram below






                                                                                                             54 mm
                                                                                 38 mm

                                                                                               105 mm
                                                                                              M4 clearance
                                                                                               120 mm

                                                                                 19 mm
                                                                                               109 mm
                                                                                              M4 clearance
          (1)   Nominal voltage (RMS/DC or AC peak)
           measured at < 10 μA (OVR 15E, OVR 30E,
           OVR 50E, OVR 110E) and < 200 μA (OVR 06E)
          (2)   Maximum working voltage (RMS/DC or AC peak)
           measured at  < 5 mA leakage (OVR 15E, OVR 30E,
           OVR 50E, OVR 110E) and  < 10 mA (OVR 06E)
          (3)   The maximum transient voltage let-through of the
           protector throughout the test (±10%), line to line &
           line to earth, both polarities. Response time < 10 ns
          (4)   Test to IEC 61000-4-5:2006, ITU-T (formerly
           CCITT) K.20, K.21 and K.45,Telcordia
           GR-1089-CORE, Issue 2:2002, ANSI TIA/EIA/
           IS-968-A:2002 (formerly FCC Part 68)
   550   551   552   553   554   555   556   557   558   559   560