Protection and safety
Data & signal protection
OVR E Series
5
Combined Category D, C, B tested protector (to BS EN 61643) suitable for
twisted pair signalling applications which require either a lower in-line
resistance, an increased current or a higher bandwidth than the OVR D Series.
Also suitable for DC power applications less than 1.25 Amps. Available for
working voltages of up to 6, 15, 30, 50 and 110 Volts. For use at boundaries up to
LPZ 0 to protect against flashover (typically the service entrance location)
through to LPZ 3 to protect sensitive electronic equipment.
Features & benefits
• Very low let-through voltage (enhanced protection to • Screen terminal enables easy connection of cable screen
IEC/BS EN 62305) between all lines - Full Mode protection to earth
• Full Mode design capable of handling partial lightning • Strong, flame retardant, ABS housing
currents as well as allowing continual operation of • Built-in DIN rail foot for simple clip-on mounting to top hat
protected equipment DIN rails
• Repeated protection in lightning intense environments • Colour coded terminals give a quick and easy installation
• Very low (1 Ω) in-line resistance allows resistance critical check - grey for the dirty (line) end and green for clean
applications (e.g. alarm loops) to be protected • Substantial earth stud to enable effective earthing
• High (1.25 A) maximum running current • Supplied ready for flat mounting on base or side
• High bandwidth enables higher frequency (high traffic or • Integral earthing plate for enhanced connection to earth
bit rate) data communications via OVR CME kit
Application Installation
Use these units to protect resistance sensitive, higher Connect in series with the data communication or signal line
frequency or running current systems, e.g. high speed either near where it enters or leaves the building or close to
digital communications equipment or systems with long the equipment being protected (e.g. within its control
signal lines. panel). Either way, it must be very close to the system’s
earth star point. Install protectors either within an existing
cabinet/cubicle or in a separate enclosure.
Accessories
Combined Mounting/Earthing kits: Weatherproof enclosures: Install in series (in-line)
OVR CME 4 Mount & earth OVR WBX 4, OVR WBX 4/GS
up to 4 protectors For use with a OVR CME 4
OVR CME 8 Mount & earth and up to 4 protectors DIRTY CLEAN
up to 8 protectors OVR WBX 8, OVR WBX 8/GS
OVR CME 16 Mount & earth For use with a OVR CME 8
up to 16 protectors and up to 8 protectors
OVR CME 32 Mount & earth OVR WBX 16/2/G From line To
up to 32 protectors For use with one or two OVR CME equipment
16 and up to 32 protectors
Earth
NOTE: Slim Line (OVR SL) and ATEX (OVR SLX) are available. For many twisted pair data and signal applications, the lower cost OVR D Series may be suitable.
For applications requiring higher current (1.25 A to 4 A) or ultra-low in-line resistance, the OVR H Series protectors may be more suitable.