Page 559 - Din prodcuts 2020
P. 559

5/115




          —
          Protection and safety
          Data & signal protection
          OVR SL 3-Wire Series


          OVR SL 3-Wire Series - Technical specification
          Electrical specification       OVR SL06/3W   OVR SL15/3W   OVR SL30/3W    OVR SL50/3W   OVR SL110/3W
          ABB order code                 7TCA085400R0328 7TCA085400R0330 7TCA085400R0331 7TCA085400R0332 7TCA085400R0329  5
          Nominal voltage  (1)           6 V           15 V          30 V           50 V          110 V
          Maximum working voltage Uc (RMS/DC)  (2)  5 V/7.79 V   11 V/16.7 V   25 V/36.7 V   40 V/56.7 V   93 V/132 V
          Current rating (signal)        500 mA
          In-line resistance (per line ±10%)  1.0 Ω
          Bandwidth (-3 dB 50 Ω system)  45 MHz
          Transient specification        OVR SL06/3W   OVR SL15/3W   OVR SL30/3W    OVR SL50/3W   OVR SL110/3W
          Let-through voltage (all conductors)   Up
                                    (3)
          C2 test 4 kV 1.2/50 μs, 2 kA 8/20 μs to    36.0 V   38.4 V   63.0 V       90.3 V        185 V
          BS EN/EN/IEC 61643-21
          C1 test 1 kV, 1.2/50 μs, 0.5 kA 8/20 μs to   26.2 V   29.4 V   51.3 V     77.2 V        175 V
          BS EN/EN/IEC 61643-21
          B2 test 4 kV 10/700 μs to BS EN/EN/IEC   16.0 V   26.8 V   45.4 V         68.3 V        165 V
          61643-21
          5 kV, 10/700 μs  (4)           17.0 V        27.5 V        46.3 V         69.1 V        170 V
          Maximum surge current
          D1 test 10/350 μs to    – Per signal wire 1.25 kA
          BS EN/EN/IEC 61643-21  – Per pair  2.5 kA
          8/20 μs to ITU-T   – Per signal wire 10 kA
          K.45:2003, IEEE   – Per pair   20 kA
          C62.41.2:2002
          Mechanical specification       OVR SL06/3W   OVR SL15/3W   OVR SL30/3W    OVR SL50/3W   OVR SL110/3W
          Temperature range              -40 to +80 °C
          Connection type                Screw terminal - maximum torque 0.8 Nm
          Conductor size (stranded)      4 mm 2
          Earth connection               Via DIN rail or 4 mm  earth terminal - maximum torque 0.8 Nm
                                                      2
          Case material                  FR Polymer UL-94 V-0
          Weight         – Unit          0.08 kg
                         – Packaged (per 10)  0.85 kg
          Dimensions                     See diagram below










                                                                                                            104.6 mm

                                                                     106.5 mm

                                                    7 mm    2  S  1              1  S  2  E




          (1)   Nominal voltage (RMS/DC or AC peak) measured at
           < 10 μA (OVR SL15/3W, OVR SL30/3W, OVR SL50/3W,
           OVR SL110/3W) and < 200 μA (OVR SL06/3W)
          (2)   Maximum working voltage (RMS/DC or
           AC peak) measured at < 1 mA leakage
          (3)   The maximum transient voltage let-through of the
           protector throughout the test (±10%), line to line &
           line to earth, both polarities. Response time < 10 ns
          (4)   Test to IEC 61000-4-5:2006, ITU-T (formerly
           CCITT) K.20, K.21 and K.45, Telcordia
           GR-1089-CORE, Issue 2:2002, ANSI TIA/EIA/
           IS-968-A:2002 (formerly FCC Part 68)
   554   555   556   557   558   559   560   561   562   563   564