Page 560 - Din prodcuts 2020
P. 560

5/116            ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS   2CHC 420 001 C0201




          —
          Protection and safety
          Data & signal protection
          OVR SL LED 4-20 mA Series






  5






                                            Combined Category D, C, B tested protector (to BS EN 61643) suitable for
                                            twisted pair 4-20 mA loop systems with innovative LED protector status
                                            indication. For use at boundaries up to LPZ 0 to protect against flashover
                                            (typically the service entrance location) through to LPZ 3 to protect sensitive
                                            electronic equipment (e.g. transmitters, monitors, controllers).


          Features & benefits
          •  Very low let-through voltage (enhanced protection to    •  Very low (1 Ω) in-line resistance for minimal system
           IEC/BS EN 62305) between all lines - Full Mode protection  interference
          •  Full Mode design capable of handling partial lightning   •  High (75 mA) maximum running current - can also be used
           currents as well as allowing continual operation of   on 10-50 mA systems (e.g. process control)
           protected equipment                                •  Screen terminal enables easy connection of cable screen
          •  Repeated protection in lightning intense environments  to earth
          •  Innovative LED indication of protection status provides   •  Strong, flame retardant, polycarbonate housing
           easy visual checking and quick maintenance         •  Built-in innovative DIN rail foot with locking feature for
          •  Ultra slim 7 mm width ideal for compact protection of    simple positioning and clip-on mounting to top hat DIN rails
                                                                    2
           large numbers of lines (e.g. process control installations)  •  4 mm  terminals allow for larger cross section wiring,
          •  Two stage removable protection module with simple quick   stranded wires terminated with ferrules or fitting two
           release mechanism allowing partial removal for easy line   wires into a single terminal
           commissioning and maintenance as well as full removal for   •  Convenient earthing through DIN foot and/or earth
           protection replacement                              terminal


          Application                                         Installation
          Use these protectors on 4-20 mA loop systems - ideal where   Connect in series with the 4-20 mA current loop either near
          installation space is at a premium and large numbers of lines   where it enters or leaves the building or close to the
          require protection, or for systems with long signal lines.  equipment being protected (e.g. within its control panel).
                                                              Either way, it must be very close to the system’s earth star
                                                              point. Install protectors either within an existing cabinet/
                                                              cubicle or in a separate enclosure.



                                                                       LINE                                                      CLEAN
                                                                                             CLEAN
                                                                          LINE
                                                                                   Lightning Barrier
                                                                                   Nominal voltage  30V
                                                                                   Max working voltage, U c 36.7V
          Accessories                                                   1          Current rating  750mA 1.0Ω 20kA 63V  3
                                                                                   In-line resistance
                                                                                   Max surge current
                                                                                   Let-through voltage, U p
          OVR SL30L/4-20/M          Weatherproof enclosure:             S           Furse Wilford Road,
                                                                                    Nottingham,
                                                                                    NG2 1EB, UK
          Module replacement        OVR WBX SLQ                                                   S
          OVR SL/B                                                      2                         4
          Base replacement
                                                                        From line        To equipment
                                                                                         To equipment
                                                                        From line
                                                                                   Earth
                                                                                    Earth
          TECHNICAL NOTE: 4-20 mA current loops can serve multiple devices over a long distance. The devices and wiring produce a voltage drop (also known as “loop
          drops”) but these do not reduce the 4-20 mA current as long as the power supply voltage is greater than the sum of the voltage drops around the loop at the
          maximum signalling current of 20 mA.For design considerations, each OVR SL30L/4-20 device installed within the loop introduces a 1.7 V loop drop.
          NOTE: The OVR SL ‘Slim Line’ Series is also available for protection of systems up to 110 V as well as 3-wire, RS 485, RTD & telecommunication
          applications (OVR SL/3W, OVR SL RS485, OVR SL RTD & OVR SL TN). The OVR SL X Series has approvals for use in hazardous areas.