          Protection and safety
          Telecom & computer line protection
          OVR Cat-5 & Cat-6 Series


          OVR Cat-5 & Cat-6 Series - Technical specification
          Electrical Specification              OVR Cat-5e      OVR Cat-5e/PoE    OVR Cat-6     OVR Cat-6/PoE
          ABB order code                        7TCA085400R0289  7TCA085400R0290  7TCA085400R0291  7TCA085400R0292     5
          Maximum working           – data  (2)  5 V
          voltage Uc  (1)                (3)
                                    – power      –              58 V             –              58 V
          Current rating                        300 mA          600 mA  (4)      300 mA         600 mA  (4)
          In-line resistance        – data  (2)  1.5 Ω
          (per line ±25%)
                                    – power      –              1.5 Ω           –                –
          Maximum data rate                     100 Mbps        100 Mbps        1000 Mbps       1000 Mbps
          Networking standards                  10/100baseT     10/100baseT     10/100/1000/    10/100/1000/
                                                                                10GbaseT        10GbaseT
                                                TIA Cat-5e      TIA Cat-5/PoE   TIA Cat-6       TIA Cat-6
                                                IEEE 802.3i     IEEE 802.3i     IEEE 802.3i     IEEE 802.3i
                                                IEEE 802.3u     IEEE 802.3u     IEEE 802.3u     IEEE 802.3u
                                                –               IEEE 802.3af    IEEE 802.3ab    IEEE 802.3ab
                                                –               IEEE 802.3at    IEEE 802.3an    IEEE 802.3an
                                                –               –               –               IEEE 802.3af
                                                –               –               –               IEEE 802.3at
          Transient specification               OVR Cat-5e      OVR Cat-5e/PoE    OVR Cat-6     OVR Cat-6/PoE
          Let-through voltage (all conductors)   Up
                                    (5)
          C2 test 4 kV 1.2/50 μs, 2 kA 8/20 μs  – line to line  120 V  120 V/116 V  (8)  120 V  120 V/116 V  (8)
          to BS EN/EN/IEC 61643-21  – line to earth  (6)  700 V
          C1 test 1 kV, 1.2/50 μs, 0.5 kA   – line to line  74 V  74 V/95 V  (8)  74 V          74 V/95 V  (8)
          8/20 μs to BS EN/EN/IEC 61643-21
                                    – line to earth  (6)  600 V
          B2 test 4 kV 10/700 μs to    – line to line  21 V     21 V/87 V  (8)  21 V            21 V/87 V  (8)
          BS EN/EN/IEC 61643-21
                                    – line to earth(6) 550 V
          5 kV, 10/700 μs  (7)      – line to line  25 V        25 V/90 V  (8)  25 V            25 V/90 V  (8)
                                    – line to earth  (6)  600 V
          Maximum surge current  (9)
          D1 test 10/350 μs to BS EN/EN/IEC 61643-21  1 kA
          8/20 μs to ITU-T K.45:2003, IEEE C62.41.2:2002   10 kA
          Mechanical specification              OVR Cat-5e,                     OVR Cat-6,
                                                OVR Cat-5e/PoE                  OVR Cat-6/PoE
          Temperature range                     -40 to +80 °C
          Connection type                       RJ45 sockets
          Cable (supplied)                      0.5 m Cat-5e UTP                0.5 m Cat-6 STP
                                                patch lead                      patch lead
          Earth connection                      M4/DIN rail
          Case Material                         FR Polymer UL-94 V-0
          Weight                 – Unit         0.15 kg
                                 – Packaged     0.2 kg
          Dimensions                            See diagram below


                                                                                               106 mm
          (1)   Maximum working voltage (DC or AC
           peak) measured at 1 mA leakage  (6)   The interfaces used in network systems incorporate
          (2)   Data pairs 1/2 and 3/6 are protected   an isolation transformer that inherently   106 mm
           as standard. Pairs 4/5 and 7/8 are   provides an inbuilt immunity to transients   106 mm
           also protected on Cat-6 barriers  between line and earth of 1,500 Volts or more              54 mm  60 mm  Depth: 24 mm
          (3)   PoE protectors transmit power   (7)   Test to IEC 61000-4-5:2014, ITU-T (formerly
                                                                                                49 mm              Fixing centres
           Mode A and Mode B power      CCITT) K.20, K.21 and K.45,Telcordia                                       49 x 54 mm,
          (4)   Based on 30W of transmitted PSE   GR-1089-CORE, Issue 6:2011, ANSI TIA/EIA/                        M3 clearance
           power, to IEEE 802.3at.      IS-968-A:2005 (formerly FCC Part 68).      54 mm  60 mm  Depth: 24 mm
          (5)   The maximum transient voltage let-through   (8)   The first number is for the data pair, with
                                                                           49 mm
                                                                          54 mm  60 mm  Depth: 24 mm  Fixing centres
           of the protector throughout the test   the second number for the power pair        49 x 54 mm,
           (±10%), line to line & line to earth. Response   (9)   The installation and connectors may   49 mm  Fixing centres   M3 clearance
                                                                                     49 x 54 mm,
           time <10 ns (on all protected pairs)  limit the capability of the protector  M3 clearance