          Protection and safety
          Data & signal protection
          OVR RS485, RS485Q & SL RS485 Series


          OVR RS485, RS485Q & SL RS485 Series - Technical specification
          Electrical specification                         OVR RS485         OVR SL RS485     OVR RS485Q
          ABB order code                                   7TCA085400R0311   7TCA085400R0310  7TCA085400R0312          5
          Nominal voltage  (1)                             15 V
          Maximum working voltage Uc (RMS/DC)  (2)         11 V/16.7 V
          Current rating (signal)                          300 mA
          In-line resistance (per line ±10%)               1 Ω
          Bandwidth (-3 dB 50 Ω system)                    45 MHz
          Transient specification                          OVR RS485         OVR SL RS485     OVR RS485Q
          Let-through voltage (all conductors)   Up
                                    (3)
          C2 test 4 kV 1.2/50 μs, 2 kA 8/20 μs to BS EN/EN/IEC 61643-21  55.0 V
          C1 test 1 kV, 1.2/50 μs, 0.5 kA 8/20 μs to BS EN/EN/IEC 61643-21  42.0 V
          B2 test 4 kV 10/700 μs to BS EN/EN/IEC 61643-21  27.2 V
          5 kV, 10/700 μs  (4)                             28.2 V
          Maximum surge current
          D1 test 10/350 μs to            – Per signal wire  2.5 kA          1.25 kA          2.5 kA
          BS EN/EN/IEC 61643-21           – Per pair       5 kA              2.5 kA           5 kA
          8/20 μs to ITU-T K.45:2003,     – Per signal wire  10 kA
          IEEE C62.41.2:2002              – Per pair       20 kA
          Mechanical specification                         OVR RS485         OVR SL RS485     OVR RS485Q
          Temperature range                                -40 to +80 °C
          Connection type                                  Screw terminal -    Screw terminal -    Pluggable 12 way screw
                                                           max. torque 0.5 Nm  max. torque 0.8 N  terminal
          Conductor size (stranded)                        2.5 mm            4 mm   2         2.5 mm 2
                                                                2
          Earth connection                                 M6 stud           Via DIN rail or 4 mm   2  Via DIN rail or M5
                                                                             earth terminal -    threaded hole in base of
                                                                             max. torque 0.8 Nm  unit
          Case Material                                    FR Polymer UL-94 V-0
          Weight                          – Unit           0.08 kg                            0.1 kg
                                          – Packaged (per 10)  0.85 kg                        1.3 kg
          Dimensions                                       See diagram below



                                            OVR RS485                              OVR RS485Q        95 mm

                                                                              54 mm             M3 clearance
                                                   38 mm
                                                                                                Depth: 18 mm
                                                                105 mm                   87 mm            69 mm
                                                               M4 clearance
                                                                                                     42 mm
                                                                120 mm
                                                   19 mm
                                                                109 mm
                                                               M4 clearance
                                                                                   OVR SL RS485

          (1)   Nominal voltage (RMS/DC or
           AC peak) measured at < 10 μA
          (2)   Maximum working voltage (RMS/DC                                                             104.6 mm
           or AC peak) measured at < 5 mA
          (3)   The maximum transient voltage let-through of the           106.5 mm
           protector throughout the test (±10%), line to line &
           line to earth, both polarities. Response time < 10 ns
          (4)   Test to IEC 61000-4-5:2006, ITU-T (formerly   7 mm    2  S  1        1  S  2  E
           CCITT) K.20, K.21 and K.45,Telcordia
           GR-1089-CORE, Issue 2:2002, ANSI TIA/EIA/
           IS-968-A:2002 (formerly FCC Part 68)