3/30             SACE EMA X 2 LOW VOLTAGE AIR CIRCUIT-BRE AKERS



          —

          Technical characteristics for protection


          trip units


          Measurement functions












          Record of values: of the parameter for each interval with time-stamping   Parameters                                   Window               Intervals             Ekip Touch     Ekip Hi-Touch  Ekip G Touch  Ekip G Hi-Touch
          Current: minimum and maximum         [A]                 I Min, I Max                                                  Fixed  synchronizable by   Duration: 5…120min
                                                                                                                                 remote               Number of intervals: 24
          Phase-phase voltage: minimum and maximum  [V]            U Min, U max
          Active power: average and maximum    [kW]                P Avg, P Max
          Reactive power: average and maximum  [kVAR]              Q Avg, Q Max
          Apparent power: average and maximum  [KVA]               S Avg, S Max

          Data logger: record of high sampling rate parameters     Parameters
          Currents                             [A]                 L1, L2, L3, Ne, Ig
          Voltages                             [V]                 U12, U23, U31
          Sampling rate                        [Hz]                1200-2400-4800-9600
          Maximum recording duration           [s]                 13.6
          Recording stop delay                 [s]                 0-10s
          Number of registers                  [no]                2 independent

          Information on trip and opening data: after a fault without auxiliary supply  Parameters
          Type of protection tripped                               eg. L, S, I, G, UV, OV
          Fault values per phase               [A/V/Hz W/var]      eg. I1, I2, I3, neutral for S protection
                                                                   V12, V23, V32 for UV protection
          Time-stamping                                            Date, time and progressive number

          Maintenance indicators                                   Parameters
          Information on last 30 trips                             Type of protection, fault values and time-stamping
          Information on last 200 events                           Type of event, time-stamping
          Number of mechanical operations  (1)  [no]               Can be associated to alarm
          Total number of trips                [no]
          Total operating time                 [h]
          Wear of contacts                     [%]                 Prealarm >80%
                                                                   Alarm = 100%
          Date of maintenance operations performed                 Last
          Indication of maintenance operation needed
          Circuit-breaker I.D.                                     Type of circuit breaker, assigned device name, serial number

          Self-diagnosis                                           Parameters
          Check of continuity of internal connections              Alarm due to disconnection: rating plug, sensors, trip coil      Note: Opening of circuit
          Failure of circuit breaker to open (ANSI 50BF)           Alarm following non-tripping of protection functions          breaker can be set in the
                                                                                                                                 event of alarm
          Temperature (OT)                                         Prealarm and alarm for abnormal temperature
          (1) with auxiliary supply present
          Note: In case of Black trip units, 0.4% In is the lowest current value detected by Emax 2