Continued from the previous page                                   ABB | SACE Emax 2
                                    YO-YC-YO2-YC2 : Connections
                                                  (1)
                                    More details are available in the website http://www.abb.com/abblibrary/DownloadCenter/, which also
                                    includes the entire circuit diagram 1SDM000091r0001.
                                    Information on assembly is available on the website http://www.abb.com/abblibrary/DownloadCenter/, in
                                    particular,
                                    for E1.2 in the kit sheets:
                                     •  1SDH000999r0502 for YO and YO2 coils
                                     •  1SDH000999r0503 for coils YC
                                    and for E2.2-E4.2-E6.2 in the kit sheets:
                                     •  1SDH001000r0502 for YO and YO2 coils
                                     •  1SDH001000r0503 for YC and YC2 coils
                                    (1)  YC2 not available for E1.2


               YU: Undervoltage coil The undervoltage coil YU controls the value of the voltage in the circuit to which it is connected.
                                    The coil opens the circuit-breaker when its energizing voltage drops below a value between 35...70%Un
                                    The circuit-breaker can be reclosed when the coil energizing voltage is between 85...110% Un.

                                    The undervoltage coil YU can in addition be used for the following purposes:
                                     •  Trip unit the circuit-breaker remotely using pushbuttons of the normally closed type.
                                     •  Activate the lock when the circuit-breaker is closed (the closing of the circuit-breaker is allowed only with
                                       the undervoltage coil energized).
                                           IMPORTANT:
                                            •  The undervoltage coil YU is incompatible with the presence of the Fail Safe device (UL
                                              circuit-breakers).
                                            •  The  undervoltage  coil  YU  is  a emergency trip  unit.  For  service  operations  use  the
                                              opening coil.
                                           NOTE: the power supply of the coil must be drawn on the supply side of the circuit-breaker
                                               or from an independent source.

                                    If the undervoltage coil trips, it is necessary, after having reset it, to wait at least 100 ms
                                           before operating the closing coil.


                                                                   D1



                                                                   D2
                                                                   YU
                                                                  YO 2


                                    YU for E1.2


                                                                 D1


                                                                 D2
                                                                 YU
                                                                YO 2



                                    YU for E2.2 - E4.2 - E6.2

                                                                                                  Continued on the next page